200 V Redundant Power Feed Configuration (single power feed, redundant power feed)
with Power Distribution Box Connection
It is necessary to arrange four PSUs, two FANUs, four Power cables (200 V IEC60320 C20) and two power
distribution boxes (200 V IEC60320 C19×3type) for 200 V Redundant Power Feed configuration (with single
power feed, redundant power feed).
When the power distribution box is used, it is necessary to secure the breaker characteristic of distribution
panel. See “
2.5 Cutoff Characteristics of Distribution Panel (At the time of connecting power distribution box)
FIGURE 2.10 200 V Redundant Power Feed Configuration (single power feed, redundant power feed) with
Power Distribution Box Connection
Number
Description
(1)
Power distribution box (200V C 19
3 type)