Chapter 7 Maintaining the Router
Removing and Replacing the Optional 2-Level AC-Input Power Shelf
7-58
Cisco 12016, Cisco 12416, and Cisco 12816 Router Installation and Configuration Guide
OL-11495-01
•
TEMP (yellow)—Indicates that the power supply is in an overtemperature
condition, causing a shut-down to occur.
Note
If the temp indicator is on, the fault indicator also goes on.
–
Verify that the power supply fan is operating properly.
–
Verify that the blower modules are operating properly.
–
If the blower modules are operating properly, replace the existing power
supply with a spare.
•
TEMP (flashing yellow—2500 W PEM only)—Indicates that a power supply
fan is locked or malfunctioning.
Note
If the temp indicator is flashing, the fault indicator also goes on.
–
Check to see if the fan is operating. Remove anything that may be
obstructing the fan.
–
If the fan is not operating, replace the power supply.
•
ILIM (2000 W PEM only) (yellow)—Indicates the power supply is operating
in a current-limiting condition.
–
Each power cord should be connected to a dedicated AC power source.
Each AC power supply operating in the nominal range of 200 to 240 VAC
requires a minimum service of 20 A, North America (or 13 A,
international).