5.- TECHNICAL FEATURES
AC Power supply
Rated voltage
85 ... 265 V ~
Frequency
50 ... 60 Hz
Consumption
2.9...6 VA
Installation category
CAT III 300 V
DC Power supply
Rated voltage
95 ...300 V
Consumption
3 ... 6 W
Installation category
CAT III 300 V
Voltage measurement circuit
Phase - Neutral
Phase-Phase
Voltage measurement margin
5 ... 300V~
7 ... 520V~
Frequency measurement margin
45 - 65 Hz
Input impedance
0.4 MΩ
Minimum measurement voltage (Vstart)
5 V ~
Maximum voltage input consumption
0.7 VA
Installation category
CAT III 300 V
Current measurement circuit
Nominal current (In)
... / 0.250 A
Current measurement margin
0...250 mA
Maximum current, impulse < 1s
In x 1.3
Minimum measurement current (Istart)
3 mA
Maximum current input consumption
0.18 VA x 4 channels
Installation category
CAT III 300 V
Measurement accuracy
Voltage measurement
0.5%
Current measurement
0.5%
Power measurement
1%
(2)
Energy measurement
1%
(2)
From 90W
Transistor output
Quantity
4
Type
NPN
Maximum voltage
24V
Maximum current
50 mA
Maximum frequency
5 pulses / sec
Pulse width
100 ms
Communications
Field bus
RS-485
Communications protocol
Modbus RTU
Speed
9600-19200-38400-57600
Stop bits
1
Parity
none
30
CVM-NET4+-MC
Instruction Manual
Summary of Contents for CVM-NET4+-MC
Page 1: ...INSTRUCTION MANUAL M056B01 03 21A Power analyzer CVM NET4 MC...
Page 2: ...2 CVM NET4 MC Instruction Manual...
Page 32: ...35 5 5 25 44 65 45 65 90 105 Figure 7 CVM NET4 MC dimensions 32 CVM NET4 MC Instruction Manual...
Page 34: ...8 CE CERTIFICATE 34 CVM NET4 MC Instruction Manual...
Page 35: ...35 Instruction Manual CVM NET4 MC...
Page 36: ...36 CVM NET4 MC Instruction Manual...