4�4�3�- CONFIGURATION OF MAXIMUM DEMAND
The
CVM-NET4+-MC
can calculate the maximum demand using the scrolling or fixed window method,
depending on the selection.
The maximum demand is simultaneously calculated in kW, kVA, A and phase current.
Table 9:Maximum demand configuration
Modbus
Address
Variable
Valid data margin
274C
Channel 1 integration time
0
to
003C
(0-60 minutes)
274D
Channel 1 integration type
0000
: Scrolling
0001
: Static
2756
Channel 2 integration time
0
to
003C
(0-60 minutes)
2757
Channel 2 integration type
0000
: Scrolling
0001
: Static
2760
Channel 3 integration time
0
to
003C
(0-60 minutes)
2761
Channel 3 integration type
0000
: Scrolling
0001
: Static
276 A
Channel 4 integration time
0
to
003C
(0-60 minutes)
276B
Channel 4 integration type
0000
: Scrolling
0001
: Static
Example
of maximum demand programming for Channel 1, with a 15-minute period in scrolling system:
TX
: NP 10 274C 0002 04
000F 0000
CRC
RX
: NP 10 274C 0002 CRC
4�4�3�1�- Reading the maximum demand configuration
The user has a Modbus command as extra information for reading the maximum demand configura-
tion:
TX
: NP 04 274C 0002 CRC
RX
: NP 04 04
000F 0000
CRC
4�4�4�- DELETING MAXIMUM AND MINIMUM VALUES
The
CVM-NET4+-MC
records all the maximum and minimum values of each measured parameter in
the Modbus/RTU variables table.
A command is available for resetting these records:
TX
: NP 05 0838 FF 00 CRC
RX
: NP 05 0838 FF 00 CRC
15
Instruction Manual
CVM-NET4+-MC
Summary of Contents for CVM-NET4+-MC
Page 1: ...INSTRUCTION MANUAL M056B01 03 21A Power analyzer CVM NET4 MC...
Page 2: ...2 CVM NET4 MC Instruction Manual...
Page 32: ...35 5 5 25 44 65 45 65 90 105 Figure 7 CVM NET4 MC dimensions 32 CVM NET4 MC Instruction Manual...
Page 34: ...8 CE CERTIFICATE 34 CVM NET4 MC Instruction Manual...
Page 35: ...35 Instruction Manual CVM NET4 MC...
Page 36: ...36 CVM NET4 MC Instruction Manual...