Table 12 (Cont�): Deleting energies
Modbus Address
Variable
Data margin
089B
Deleting Channel 2- 1S1 Single phase Energies
FF
089C
Deleting Channel 2- 2S1 Single phase Energies
FF
089D
Deleting Channel 2- 3S1 Single phase Energies
FF
089E
Deleting Channel 3- 1S1 Single phase Energies
FF
089F
Deleting Channel 3- 2S1 Single phase Energies
FF
08A0
Deleting Channel 3- 3S1 Single phase Energies
FF
08A1
Deleting Channel 4- 1S1 Single phase Energies
FF
08A2
Deleting Channel 4- 2S1 Single phase Energies
FF
08A3
Deleting Channel 4- 3S1 Single phase Energies
FF
Example
of a write command. Deleting Channel 3 three-phase energies.
TX
: NP 05 0846 FF00 CRC
RX
: NP 08 0846 FF00 CRC
4�4�8�- CONFIGURATION AND USE OF DIGITAL OUTPUTS
4�4�8�1�- Forcing digital outputs
The device features four digital outputs that can be remotely managed in both their opening and clos-
ing functions.
Table 13:Configuration and use of digital outputs, forcing digital outputs
Use of Digital Outputs
Modbus Address
Output
Open / Close
000F
Output 1
00 / FF
0010
Output 2
00 / FF
0011
Output 3
00 / FF
0012
Output 4
00 / FF
Example
of forcing Digital Output number 1
:
TX
: NP 05
000F
FF 00 CRC
RX
: NP 05 000F FF 00 CRC
4�4�8�2�- Reading the digital output status
The user can request a reading of the digital output status via Modbus/RTU using the following sen-
tence:
TX
: NP 04 4E21 0001 CRC
RX:
NP 04 04 02 000 CRC
Converting to Binary - 1 Byte (0 = Open / 1 = Closed)
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
-
-
-
-
Out 4
Out 3
Out 2
Out 1
17
Instruction Manual
CVM-NET4+-MC
Summary of Contents for CVM-NET4+-MC
Page 1: ...INSTRUCTION MANUAL M056B01 03 21A Power analyzer CVM NET4 MC...
Page 2: ...2 CVM NET4 MC Instruction Manual...
Page 32: ...35 5 5 25 44 65 45 65 90 105 Figure 7 CVM NET4 MC dimensions 32 CVM NET4 MC Instruction Manual...
Page 34: ...8 CE CERTIFICATE 34 CVM NET4 MC Instruction Manual...
Page 35: ...35 Instruction Manual CVM NET4 MC...
Page 36: ...36 CVM NET4 MC Instruction Manual...