4�4�8�3�- Configuration of digital outputs
Digital outputs, in addition to being remotely managed, can be used as alarm elements, associated
with an electric variable by a maximum or minimum value, or can carry out the power impulse function
associated with any power consumption parameter (active or reactive).
The following input table is provided to programme them
:
Table 14:Configuration of Channel 1 digital output
Digital output 1
Modbus Address
Variable
Valid data margin
2AF8, 2AF9
MAX value or W•h imp
Hexadecimal value
2AFA, 2AFB
MIN value
Hexadecimal value
2AFC
Variable number
00
(See
)
2AFD
Delay / Pulse width
0
to
270F
(9999 Decimal)
Note:
When a power variable is selected, the unit automatically recognises the power impulse function
and applies the w·h value of the first record. The pulse width value is in milliseconds
Example of alarm programming by maximum and minimum value with voltage VL1:
Programme a maximum value of 240 V and a minimum value of 200 V (the voltage value must be sent
multiplied by 10
(as shown in
)
, and a delay of 10 s
.
Maximum value: 2400 (Decimal) → 00000960 (Hexadecimal)
Minimum value: 2000 (Decimal) → 000007D0 (Hexadecimal)
Delay: 10 (Decimal) → 000A (Hexadecimal)
Variable Number: 01 (Decimal) → 01 (Hex)
Write:
TX
: NP 10
2AF8
0006 0C
00000960 000007D0 000A 0010
CRC
RX
: NP 10 2AF8 0006 CRC
Read:
TX
: NP 04 04
2AF8
0006 CRC
RX
: NP 04 0C
00000960 000007D0 000A 0010
CRC
18
CVM-NET4+-MC
Instruction Manual
Summary of Contents for CVM-NET4+-MC
Page 1: ...INSTRUCTION MANUAL M056B01 03 21A Power analyzer CVM NET4 MC...
Page 2: ...2 CVM NET4 MC Instruction Manual...
Page 32: ...35 5 5 25 44 65 45 65 90 105 Figure 7 CVM NET4 MC dimensions 32 CVM NET4 MC Instruction Manual...
Page 34: ...8 CE CERTIFICATE 34 CVM NET4 MC Instruction Manual...
Page 35: ...35 Instruction Manual CVM NET4 MC...
Page 36: ...36 CVM NET4 MC Instruction Manual...