8.- TECHNICAL FEATURES
Power supply
Mode
Self-powered
Voltage Measurement
Connection
Single-phase
Reference voltages
230 V ~
Frequency
CEM-C12c
50 / 60 Hz
CEM-C12c-MID
50 Hz
Power consumption
≤ 12 VA, ≤ 1 W
Current measurement
Rated Current (In)
CEM-C12c
5 A
CEM-C12c-MID
0.25 ... 5 A
Maximum current (Imax)
100 A
Starting current
0.004 Ib
Accuracy
Accuracy
CEM-C12c
Class 1 (IEC 62053-21)
CEM-C12c-MID
Class B (EN50470)
RS-485 Communications
Bus
RS-485
Protocol
Modbus RTU
Baud rate
9600 - 19200 - 38400 - 115200 bps
User interface
Display
LCD
Maximum counter value
99999.99 kWh
Keys
1 key
LED (kWh)
1000 imp/kWh ( width: 90 ms)
Environmental features
Operating temperature
-25ºC... +70ºC
Storage temperature
-30ºC... +70ºC
Relative humidity (maximum value)
95%
Average humidity value of year
75%
Mechanical features
Dimensions ( Figure 12)
90 x 18 x 72 mm
Weight
0.10 kg
Enclosure
PTB + 15% GF
Protection degree IP
IP51
Use
Indoor
Connections
RS-485 (B-, S, A+)
≤ 1.5 mm
2
0.4 Nm
Flat, PH2
Neutral (N)
≤ 1.5 mm
2
0.4 Nm
Flat, PH2
Measure (L, LOAD)
≤ 22 mm
2
≤ 3 Nm
Flat, PZ2
21
Instruction Manual
CEM-C12c
Summary of Contents for CEM-C12c
Page 1: ...INSTRUCTION MANUAL M362B01 03 22A Multifunctional Energy Meter CEM C12c CEM C12c MID...
Page 2: ...2 CEM C12c Instruction Manual...
Page 24: ...11 CE CERTIFICATE 24 CEM C12c Instruction Manual...
Page 25: ...25 Instruction Manual CEM C12c...
Page 26: ...26 CEM C12c Instruction Manual...
Page 27: ...27 Instruction Manual CEM C12c...