CIAT XtraConnect 2 Installation, Operation, Commissioning, Maintenance Download Page 59

EN - 58 

25.2 Transmission mode. 

 Serial, asynchronous, half duplex, RTU mode. 

- 1 start bit.  
- 8 data bits. 
- The parity is set via parameter P702, 
- The number of stop bits is set via parameter P703, 
- The transmission speed is set via parameter P701, 
- The unit number on the Bus is set via parameter P705. 

 Coding of analogue values. 

Standard 32-bit IEEE format (2 registers). 
Order of values: 
 

- If P704 = No: low order, high order. 

 

- If P704 = Yes: high order, low order. 

 Function codes used. 

1 or 2: read n bits. 

3 or 4: read multiple registers (16 bits) 
5: write one bit ………….. 
6: write register function… 
8: read diagnostics counters. 
11: read event counter. 
15: write n bits. 
16: write multiple registers (16 bits) 

Note:

 the write functions are enabled if parameter P103 is set to 

"Remote, BMS…" 

 Error codes: 

1: function code unknown. 
2: address incorrect. 
3: data error. 

 

25.3 Customer-accessible register 

 

 

Register No. 

hexadecimal 

Register 

No. 

decimal 

Description Format 

Type 

Setting 

Registers accessible in read-only mode (Functions 3 or 4) 

0x01 

Controller name 

Decimal 

Read-only 

36 = Xtra Connect 2 

0x02 

Actual operating mode 

Decimal 

Read-only 

 0 = off; 1 = cooling; 2 = heating 

0x3 and 0x4 

3 and 4 

Outdoor temperature Float 

Read-only 

 

 

0x5 and 0x6 

5 and 6 

Control setpoint 

Float 

Read-only 

  

0x7 and 0x8 

7 and 8 

Evaporator inlet temperature Float 

Read-only 

 

 

0x9 and 0xa 

9 and 10 

Evaporator outlet temperature Float 

Read-only 

 

 

0xb and 0xc 

11 and 12 

Condenser inlet temperature Float 

Read-only 

 

 

0xd and 0xe 

13 and 14 

Condenser outlet temperature 

Float 

Read-only 

 

0xf and 0x10 

15 and 16 

Manifold outlet temperature (modules 1 and 2) Float 

Read-only 

 

0x11 and 0x12 

17 and 18 

Master/slave manifold outlet temperature (2 machines) 

Float 

Read-only 

 

0x13 

19 

Number of stages on 

Char 

Read-only 

 

 

 

 

 

 

 

0x20 and 0x21 

32 and 33 

P285 Heating mode runtime (in hours) 

Float 

Read-only 

  

0x22 and 0x23 

34 and 35 

P286 Cooling mode runtime (in hours) 

Float 

Read-only 

  

0x24 and 0x25 

36 and 37 

P287 Pump 1 runtime (in hours) 

Float 

Read-only 

  

0x26 and 0x27 

38 and 39 

P288 Pump 2 runtime (in hours) 

Float 

Read-only 

  

0x28 and 0x29 

40 and 41 

P310 Number of compressor 1 starts 

Float 

Read-only 

  

0x2a and 0x2b 

42 and 43 

P311 Compressor 1 runtime 

Float 

Read-only 

  

0x2c and 0x2d 

44 and 45 

P313 Number of compressor 2 starts 

Float 

Read-only 

  

0x2e and 0x2f 

46 and 47 

P314 Compressor 2 runtime 

Float 

Read-only 

  

0x30 and 0x31 

48 and 49 

P340 Number of compressor 3 starts 

Float 

Read-only 

  

0x32 and 0x33 

50 and 51 

P341 Compressor 3 runtime 

Float 

Read-only 

  

 

 

 

 

 

 

0x50 and 0x51 

80 and 81 

Voltage between phases 1 and 2 (module 1) 

Float 

Read-only 

  

0x52 and 0x53 

82 and 83 

Voltage between phases 2 and 3 (module 1) 

Float 

Read-only 

  

0x54 and 0x55 

84 and 85 

Voltage between phases 1 and 3 (module 1) 

Float 

Read-only 

  

0x56 and 0x57 

86 and 87 

Current input (module 1) 

Float 

Read-only 

  

0x58 and 0x59 

88 and 89 

Instantaneous power consumption (module 1) 

Float Read-only 

 

 

0x5a and 0x5b 

90 and 91 

Module 1 power consumption (kW) 

Float 

Read-only 

Write 0 to reset modules 1 and 2 

0x5c and 0x5d 

92 and 93 

Voltage between phases 1 and 2 (module 2) 

Float 

Read-only 

  

0x5e and 0x5f 

94 and 95 

Voltage between phases 2 and 3 (module 2) 

Float 

Read-only 

  

0x60 and 0x61 

96 and 97 

Voltage between phases 1 and 3 (module 2) 

Float 

Read-only 

  

0x62 and 0x63 

98 and 99 

Current input (module 2 

Float 

Read-only 

  

Registers accessible in read-only mode (Functions 3 or 4) 

0x64 and 0x65 

100 and 101 

Instantaneous power consumption (module 2) 

Float Read-only 

 

 

0x66 and 0x67 

102 and 103 

Module 2 power consumption (kW) 

Float 

Read-only 

Write 0 to reset modules 1 and 2 

0x68 and 0x69 

104 and 105 

Total current input 

Float 

Read-only 

  

0x6a and 0x6b 

106 and 107 

Total instantaneous power consumption 

Float 

Read-only 

  

0x6c and 0x6d 

108 and 109 

Total power consumption (kW) 

Float 

Read/Write 

Write 0 to reset modules 1 and 2 

Registers accessible in read mode (Functions 3 or 4) and write mode (Function 16) 

0x101 and 0x102 

257 and 258 

P121 Cooling setpoint 1 

Float 

Read/Write 

  

0x103 and 0x104 

259 and 260 

P122 Cooling setpoint 2 

Float 

Read/Write 

  

0x105 and 0x106 

261 and 262 

P123 Heating setpoint 1 

Float 

Read/Write 

  

0x107 and 0x108 

263 and 264 

P124 Heating setpoint 2 

Float 

Read/Write 

  

Summary of Contents for XtraConnect 2

Page 1: ...de signalisation microprocesseurs pour refroidisseurs de liquide et pompe chaleur Microchip and LCD display electronic regulation and signaling electronic module for liquid coolers and heat pumps Ele...

Page 2: ...enu 20 5 5 Unit parameters menu 21 5 6 Adjustment parameters menu 21 5 7 Reading parameters menu 22 5 8 Fault memory menu 23 5 9 Test mode menu 24 5 10 TIME SCHEDULES menu 25 5 11 COMMUNICATION Menu 2...

Page 3: ...water supply only 45 18 5 Water return control for storage CRISTOPIA 47 18 6 Modulating control water return only 47 18 7 Automated self regulating control 48 18 8 Compensation 48 19 CONDENSING PRESSU...

Page 4: ...om power lines 400 V or a remote control line 230 V In the case of distances of over 6 m use a shielded cable connected to the earth on the unit Maximum distance 25 m 1 6 Connection of the communicati...

Page 5: ...Outputs Control stage control Pump control General fault Consoles Local console The controls on the local console are enabled regardless of the value of P103 All faults can be reset from the FAULT ME...

Page 6: ...following message to appear for 3 seconds 2 2 Description of the motherboard SWITCH W3 End of line resistance for two wire RS485 link The switch must be set to the left for the last unit on the loop...

Page 7: ...CK J9 Link for chiller or MULTICONNECT TERMINAL BLOCK J10 Remote control console relay board link AEROCONNECT TERMINAL BLOCK J11 BMS link TERMINAL BLOCK J12 Local console link TERMINAL BLOCK J13 Link...

Page 8: ...l outputs 3 25 valve output compressor 1 4 25 valve and intake valve neutral 5 Compressor 1 intake valve output 6 Compressor 1 exhaust valve output 7 Compressor 1 liquid valve and exhaust valve neutra...

Page 9: ...nd 4 2 Circuit 3 fault output 3 Available 4 Available 5 Phase input common to terminals 6 7 and 8 6 Evaporator defrost heater output 7 Desuperheater heater output 8 Available TERMINAL BLOCK J11 on off...

Page 10: ...d on unit Shield To expansion board XTRACONNECT 2 motherboard Unit 2 Local console See detail B MULTICONNECT motherboard Shield RS485 link to BMS Modbus protocol XTRACONNECT 2 ADD3 board Unit 1 module...

Page 11: ...r 3 protection fault 47 48 Compressor 3 operation 49 50 Circuit 3 discharge temperature fault 51 52 Compressor 3 minimum superheat fault 53 54 Compressor 3 lubrication fault 3 ACCESS LEVELS Xtraconnec...

Page 12: ...entering the access codes The digits in the access codes are replaced by the symbol When the or button is pressed this symbol is replaced by the digit 0 The digits in the code can then be selected us...

Page 13: ...able Access level No Description Setting Default Display conditions MACHINE CONFIGURATION 3 1 Refrigerant type R134a R134a 3 2 Unit type 1 Water to water 2 Air to water 2 3 3 Number of circuits 2 3 2...

Page 14: ...ntial 5 to 6 C resolution 0 5 10 C 3 51 Discharge temperature limit 60 to 6 C resolution 1 115 3 52 Water line frost protection limit 25 to 6 C resolution 0 1 2 3 54 HP fault threshold 15 to 45 bar re...

Page 15: ...tion 1 5 If P131 Yes 1 134 Maximum setpoint at end of drift The highest setpoint if P120 1 or Setpoint if P120 1 to 60 C resolution 0 1 P123 If P131 Yes Control 2 141 Control mode 1 Return 2 Water sup...

Page 16: ...esolution 1 DISABLED If P2 Water to water and Air to water and P119 Heating only 3 225 2 Max outdoor air temp in HEATING mode 5 to 25 C resolution 1 DISABLED If P2 Water to water and P119 Cooling only...

Page 17: ...If P2 1 or 2 or 3 cooling mode 1 327 Circuit 1 subcooling C If P2 1 or 2 or 3 cooling mode Circuit 2 1 330 Circuit 2 HP If P2 Air to water and P3 2 1 330 1 Circuit 2 HP control setpoint If P3 2 and In...

Page 18: ...put check Open Closed 1 418 Manual HP1 pressure switch input check Open Closed 1 421 Compressor 2 fault check Open Closed 1 422 Manual HP2 pressure switch input check Open Closed If P3 2 1 425 Compres...

Page 19: ...n number 1 556 Console version number 1 557 2 ADD3 board version number If P3 3 1 557 3 ADD3 board version number circuit 3 If P3 3 1 557 4 ADD1 board version number circuit 3 P3 3 1 570 SO order numb...

Page 20: ...K lower than that set in a higher access level 5 3 Unit status menu The unit status is displayed at power up and automatically reappears if the console is not used after a period of one hour To enter...

Page 21: ...C U I T X S T O P L P x F A U L T C I R C U I T X S T A T E A N T I S H O R T C Y C L E X x m n x x s C O M P X U N A V A I L A B L E M I N S T O P x m n x x s C I R C U I T 2 C I R C U I T 3 C O O L...

Page 22: ...draulic mode is installed P25 Number of pumps 1 or 2 P26 0 10 V programmable output used to control a three way valve on the hot water circuit P28 Master slave control of two parallel connected units...

Page 23: ...P187 Circuit 2 fan stage differential see section 18 P188 Circuit 2 fan interstage differential see section 18 P189 Circuit 3 fan stage differential see section 18 P190 Circuit 3 fan interstage diffe...

Page 24: ...pressure switch 1 input state P421 Stage 2 fault input state P422 High pressure switch 2 input state P425 Stage fault input state P426 Stage load shedding input state P427 High pressure switch 3 inpu...

Page 25: ...E R G E N C Y S T O P x C U S T O M E R F A U L T x C I R C U I T H P x x C I R C U I T L P x x C O M P R E S S O R M O T O R X x L U B R I C A T I O N X x D I S C H A R G E T C I R C X x D E S U P E...

Page 26: ...of rotation is correct If not check the power supply wiring This function is available in all operating states even if faults occur 5 10 TIME SCHEDULES menu To enter the TIME SCHEDULES menu use the or...

Page 27: ...2 console Parameter A116 CIAT water chiller link is not accessible via the Xtraconnect 2 console because setting A116 to No will cut the link with the console Parameter A250 is not accessible because...

Page 28: ...mps If the contact is open for more than 3 seconds If 3 shutdowns occur in 1 hour If a fault occurs Pumps turned off Compressors turned off 3 minute time delay Fault stored in fault memory Machine and...

Page 29: ...Display Resetting Once the input closes acknowledge the fault by pressing RESET on the console If P24 Yes and P25 2 unit with hydraulic module and two pumps Operation Detected by opening of contact on...

Page 30: ...ox Operation The reset outputs on the SE protection box are enabled when power is applied to the board These three inputs monitor the operation of each compressor They are associated with the operatio...

Page 31: ...lly then acknowledge the fault by pressing RESET 6 13 LP fault on circuit 1 2 or 3 Operation If the pressure measured by the LP pressure transmitter is P55 the Xtraconnect 2 controller records an LP f...

Page 32: ...ly The number of faults over a 24 hour period is managed Display Resetting If the number of faults in 24 hours 3 the fault is automatically acknowledged after 120 seconds and the fault input opens If...

Page 33: ...arts up Minimum superheat fault If the superheat value P307 P337 or P367 drops below the minimum superheat limit value P44 for 1 minute the compressor is shut off and the minimum superheat error messa...

Page 34: ...o the setpoint value heating and cooling and a fault is displayed Display the outdoor air temperature display range 40 to 99 9 C resolution 0 1 K If the sensor wire is cut and a short circuit occurs a...

Page 35: ...nt leaks before turning on stages The slopes of the sensors are adjusted using parameters P30 to P41 Important The pressure values given are for relative pressure Short circuit faults will be detected...

Page 36: ...in on off operation if neither has a fault The second available pump is turned on if a fault occurs on either pump The machine is turned off if a fault occurs on both pumps Unless a pump fault occurs...

Page 37: ...er an electric liquid valve or to interlock the electronic expansion valve with the compressor If the outputs are used for either purpose they must be controlled by a relay The liquid valve outputs ar...

Page 38: ...nimum off time This function limits the number of compressor starts to 4 per hour It is disabled in testing mode Important the compressors must be stopped for at least 5 minutes even during testing mo...

Page 39: ...enable this function simply enter a value between 5 C and 25 C and press OK 15 7 3 Maximum air temperature limit in cooling mode This parameter can be set to between 35 C and 50 C in 1 increments Def...

Page 40: ...llustrated below 2 circuits on 1 circuit on A limitation logic is used in cooling mode to start up the machine and if the valve opening time is too long to reduce the compressor capacity for 2 minutes...

Page 41: ...aults and is authorised to operated The first machine to start is one that is available and has run for the shortest time Runtime balancing After every 50 hours of machine operation the system switche...

Page 42: ...achine If it is shut off On Off by automatic operation control or a fault has occurred on it the slave machine will operate using its own setpoint and its own sensors Supply control A sensor must be a...

Page 43: ...time schedule on the slave machine will become inaccessible 17 5 Unit status menu If there are no general faults and the automatic operation inputs are closed a submenu overrides the fault message is...

Page 44: ...erating mode if the change is confirmed by pressing On Off or if the automatic control input is open Or the mode change is not confirmed contact returns to initial state and the unit resumes its initi...

Page 45: ...o or outdoor sensor fault Control setpoint P121 if on off input open Control setpoint P122 if on off input closed If P127 Yes law based on outdoor temperature and there are no outdoor sensor faults Fi...

Page 46: ...ue of the signal becomes less than 4 mA the value of the setpoint will not drop below the minimum setpoint 18 3 2 Setpoint based on outdoor temperature water law In cooling mode P127 Yes Slope adjustm...

Page 47: ...ulse If e 1 5 Stage 2 turns on and stage 1 at full capacity If 1 5 e 2 Stage 2 intake pulse If e 2 Stage 3 turns on and stages 1 and 2 at full capacity If 1 e 2 5 Stage 3 intake pulse If e 2 5 Stage 3...

Page 48: ...141 If P154 Yes Storage control is enabled The control mode is managed based on the setpoint selected If setpoint 1 is selected the control remains standard and the mode supply return is selected via...

Page 49: ...nfiguring the compensator coefficient The compensator coefficient can be set to between 0 1 and 1 parameter P150 If the compensator coefficient 1 the function is disabled If the water return temperatu...

Page 50: ...tages Common fans 3 and 4 will be controlled respectively by standard stages 3 and 4 on circuit 1 LX 3600 3900 with three and a half V frame condenser fan modules on both circuits 6 single speed stage...

Page 51: ...2 3 Circuit 2 2 3 stages MC05 MC07 MC06 MC08 1 2 3 2150 Circuit 1 2 V 3 stages MC01 MC03 MC02 MC04 1 2 3 Circuit 2 2 V 3 stages MC05 MC07 MC06 MC08 1 2 3 2500 Circuit 1 2 V 3 stages MC01 MC03 MC02 MC...

Page 52: ...odules per circuit 1 stage 3 fans with speed control 3 single speed stages same as standard 4 V frame condenser fan modules per circuit 1 stage 4 fans with speed control 3 single speed stages same as...

Page 53: ...speed controlled fans and three stages of four on off fans per circuit 19 3 Condensing pressure control on 3 circuit machines Three circuit machines are always made up of two separate modules machines...

Page 54: ...and terminals 2 3 on J3 closed On The HP control setpoint then becomes equal to P181 P193 The stage differentials P185 P187 and P189 remain at 3 5 bar The function that forces on all the fans is disa...

Page 55: ...he antifreeze water temperature and the evaporating temperature compressor suction saturation P70 6 C by default if P52 2 or P70 8 if P52 2 and adjustable between 0 to 10 resolution 0 5 This control i...

Page 56: ...he module on which they occur not the entire machine Water outlet sensor faults are also managed independently on the two modules Also if the manifold water outlet sensor is controlled and a fault occ...

Page 57: ...g the control mode the Selected Days submenu appears Press OK then select the days Press to enable a day and to disable it The schedules are set in the following order start hour start minute end hour...

Page 58: ...August off Schedule 1 MTWTF Schedule 2 MTWTF Setpoint 1 Setpoint 1 Setpoint 2 Setpoint 2 Result State MTWTF State MTWTF Setpoint 1 Setpoint 1 Setpoint 2 Setpoint 2 As Saturday and Sunday are not selec...

Page 59: ...0x27 38 and 39 P288 Pump 2 runtime in hours Float Read only 0x28 and 0x29 40 and 41 P310 Number of compressor 1 starts Float Read only 0x2a and 0x2b 42 and 43 P311 Compressor 1 runtime Float Read only...

Page 60: ...te Read only 1 on 0x08 8 Not used 0x09 9 Not used 0x0a 10 Not used 0x0b 11 Not used 0x0c 12 Not used 0x0d 13 Energy limiter on Read only 1 on 0x0e to 0x0f reserved 0x10 16 General fault summary 1 faul...

Page 61: ...ult Read only 1 Fault 0x5a 90 Circuit 1 LP sensor fault Read only 1 Fault 0x5b 91 Circuit 1 suction sensor fault Read only 1 Fault 0x5c 92 Circuit 1 liquid sensor fault Read only 1 Fault 0x5d 93 ADD3...

Page 62: ...ult 0x159 345 Compressor 3 discharge fault Read only 1 Fault 0x15a 346 Not used Read only 1 Fault 0x15b 347 Not used Read only 1 Fault 0x15c 348 Expansion valve fault circuit 3 Read only 1 Fault 0c15d...

Reviews: