EN - 45
P133
P132
P134
t0
t0 + T
X1
X2
Control setpoint
value
P123 or P124
setpoint
Outdoor air
temperature
SETPOINT
Displayed if P120 = 3 and cooling mode activated
If setpoint adjustment based on outdoor temperature = No or there is an outdoor sensor fault, Control setpoint = result of diagram 2.
If setpoint adjustment based on outdoor temperature = Yes and there are no faults on the outdoor sensor, The derived setpoint is calculated
using the outdoor temperature. The result of diagram 2 is taken as the setpoint (P121 or P122).
If P120 is set to '3', P127 automatically switches to 'No
- To reverse the direction of the slope, simply set P125.1
>
P126.1 with a minimum difference of 5 K.
Important note about this function:
operating problems may occur if parameters P127 and P131 are set to 'Yes' and the controller delivering
the 4-20 mA signal has its own function for shifting the setpoint based on the outdoor temperature.
If the minimum value of the signal becomes less than 4 mA, the value of the setpoint will not drop below the minimum setpoint.
18.3.2 Setpoint based on outdoor temperature - water law
In cooling mode
(P127 = Yes)
Slope adjustment in COOLING mode
Associated parameters:
-
P128
:
Outdoor air temperature corresponding to start of drift.
- P129: Outdoor air temperature corresponding to end of drift.
- P130: Setpoint value at end of drift.
- P121 or P122: Control setpoint.
In heating mode
(P131 = Yes)
Slope adjustment in HEATING mode
Associated parameters:
-
P132
:
Outdoor air temperature corresponding to start of drift.
-
P133
:
Outdoor air temperature corresponding to end of drift.
- P134: Maximum setpoint value at end of drift.
- P123 or P124: Control setpoint.
18.4 Definition of the controller for PID control (water supply only)
The conduction time is the time the controller moves the actuator.
P 1 2 5 . 1 S E T P O I N T F O R 4 m A
C O O L I N G - x x , x °
P 1 2 6 . 1 S E T P O I N T F O R 2 0 m A
C O O L I N G - x x , x °
P130
P128
P129
P130
P128
P129
Control setpoint value
P121 or
P122
setpoint
Outdoor air
temperature
Control setpoint value
P121 or
P122
setpoint
Outdoor air
temperature