EN - 49
Refrigerating circuit 2
Refrigerating circuit 1
4 ‘common’
3 ‘common’
Refrigerating circuit 2
Refrigerating circuit 1
or
or
HP bar
or
or
HP bar
LX 2800:
3 V-frame condenser fan modules per circuit = 5 single-speed stages
LX 3050 - 3500 with three-and-a-half V-frame condenser fan modules on one circuit and two-and-a half V-frame condenser fan modules on
the other = 6 single-speed stages
'Common' fans 3 and 4 will be controlled, respectively, by standard stages 3 and 4 on circuit 1
LX 3600 - 3900
with three-and-a half V-frame condenser fan modules on both circuits = 6 single-speed stages
'Common' fans 3 and 4 will be controlled, respectively, by standard stages 3 and 4 on circuit 1
On LX 3050-3900 units, the common fans are controlled by the circuit with the highest high pressure.
LX 4200 - 4500 - 4800
with 4 V-frame condenser fan modules = 6 single-speed stages