EN - 6
Filters
M5 HEE filter
F7 HEE filter
F9 HEE filter
Thickness: 48 mm
Thickness: 48 mm
Thickness: 48 mm
Fire rating: M1
Fire rating: M1
Fire rating: M1
Single filtration
Sizes
1000
2000
3000
5000
7500
Filter Dimensions x Number of cells/
air flow
(704x327x48) x 1
(452x435x48) x 2
(552x535x48) x 2
(466x685x48) x 3
(566x835x48) x 3
Dual filtration
When dual-stage filtration is installed, the two stages of cells are installed on the same runner.
Recommended fouling level value
The pressure switches installed enable a filter fouling warning to be issued. They are factory-set, based on:
• the unit size
• the selected flow rate
• the filter efficiency
The graphs below give values which enable the actuation threshold for the pressure switches to be defined based on the selected
flow rate.
M5
ΔP
(Pa)
Qv (m³/h)
0
10
20
30
40
50
60
70
80
90
100
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
1000
2000
3000
5000
7500
F7
0
20
40
60
80
100
120
140
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
ΔP
(Pa)
Qv (m³/h)
1000
2000
3000
5000
7500
F9
0
50
100
150
200
250
300
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
ΔP
(Pa)
Qv (m³/h)
1000
2000
3000
5000
7500