Changeover thermostat for mixed coil:

The customer is responsible for installation on the hydraulic system. The changeover thermostat 
installed on the pipe must be integrated into the insulation of the hydraulic pipe. 

Technical characteristics

Min. WINTER temp.: 28 °C
Min. SUMMER temp.: 18 °C
Breaking capacity: 5(3) A.
Cable length: 2500 mm

Damper

The damper is not protected against the weather if the canopy option has not been selected.

4.  INSTALLATION & CONNECTIONS

The installation of the equipment must comply with the regulations and standards of the recipient country.

Ensure all electrical components are earthed.

The equipment must not be accessible to the public.

Special recommendations:

•  Connections must not place mechanical stresses on the unit.
•  Keep all inspection doors closed while the unit is operating
•  It must not be possible to access the fans via the connection frames for the unit. If there is a direct air intake, a grille must be 

fitted, as a minimum.

•  If fitted outdoors, the units must be installed so as to withstand the climate conditions in the installation location (risk of snow: 

height from ground/risk of wind: suitable mountings, gooseneck type electric connection to the unit, etc.).

Flexible sleeve

INSTALLATION OUTDOORS

The installation of a dual-flow unit outdoors requires a roof and a canopy to be fitted; these are usually supplied mounted* and 
adapted to suit each configuration.
(* supplied in kit form if delivery of the elements assembled is not possible)

Fitting the roofs

The roofs for units are designed to provide sufficient protection against adverse weather conditions, as they overlap the edge of 
the unit by 80 mm.

BLACK wire (winter)

IVORY wire (shared)

BLUE wire (do not use)

Summary of Contents for Floway Access 1000

Page 1: ...FLOWAY ACCESS 03 2019 EN75466664 02 Instruction manual Manuel d instructions Benutzerhandbuch Manualdeinstrucciones Instructiehandboek...

Page 2: ...CONTENTS PAGE 1 RECEIPT 3 2 HANDLING 3 3 DESCRIPTION OF THE UNIT TECHNICAL CHARACTERISTICS 4 4 INSTALLATION CONNECTIONS 9 5 SYSTEM START UP 16 6 MAINTENANCE SERVICE INTERVALS 17 7 PROBLEMS CAUSES SOLU...

Page 3: ...must be confirmed to the Carrier by registered letter within three business days The comments conditional and pending unwrapping shall have no value The client must unwrap the goods in the presence o...

Page 4: ...BSORBEE INPUT INTENSITE CURRENT POIDS WEIGHT SERVICE R f Produit Item Ref An Year N Serie Serial Nbr ELEC ELEMENT P ABSORBEE INPUT BATTERIE HEAT REGIME D signation Description Composant Composant BATT...

Page 5: ...Indoor coil hydraulic electric or DX 8 VRF electrics box option TECHNICAL CHARACTERISTICS Air flow rates Size Minimum flow rate m h Nominal Flow Rate m h Maximum flow rate m h DX coil Other coils Cool...

Page 6: ...value The pressure switches installed enable a filter fouling warning to be issued They are factory set based on the unit size the selected flow rate the filter efficiency The graphs below give value...

Page 7: ...exhaust Sizes 1000 2000 and 3000 are available in an aluminium or polypropylene version refer to the equipment selection sheet to find out the type of fan used Aluminium wheel Sizes 1000 2000 3000 500...

Page 8: ...rect level for enclosed spaces 1000 1100 ppm Tolerable level for enclosed spaces 5000 ppm Upper limit for 8 hours of exposure The CO2 sensor provides an operating range of 0 to 2000 ppm and must be in...

Page 9: ...t Keep all inspection doors closed while the unit is operating It must not be possible to access the fans via the connection frames for the unit If there is a direct air intake a grille must be fitted...

Page 10: ...following diagram 4 8 sealed rivet or 4 2 self drilling screw sealed washer Side rail 22 2 blanking cover Roof 4 8 self drilling screw Fitting the canopy without damper The upper panel will be assembl...

Page 11: ...ular 2000 737 304 494 476 698 5 2x240 2x363 3 4 3000 1188 5 358 579 560 1150 2x265 3x340 5 3 Rectangular 5000 1488 5 390 669 650 1149 2x310 6x220 6 7 7500 1788 5 528 869 841 1750 2x405 5x324 12 2 CONN...

Page 12: ...onnections IN The diameter of the condensate tube on all the pans is 16 mm 1 row coil Sizes 1000 2000 3000 5000 7500 connections mm 4 way valve Valve inlet G 1 2 G 1 2 G 3 4 G 3 4 G 1 Valve outlet G 1...

Page 13: ...ct switch size OT40 40 A OT63 63 A Max terminal section mm2 0 75 to 10 1 5 to 35 Torque Value N m 0 8 2 Connect the unit s electrics to the power network as per the table above Connection to the machi...

Page 14: ...B4 B1 7 TEMPERATURE INTRODUCTION 38 B4 B2 10 39 B5 B1 11 TEMPERATURE AIR NEUF 40 B5 B2 12 Customer cable grommet NB the maximum section of the stripped wire is 1 5 mm and 0 5 mm for a wire with an en...

Page 15: ...12 Digital inputs X2 _ b 13 Th Tune power supply 2 wires Machine terminal block Notes Inlet Outlet X2 _ b 14 24V power supply pLAN X2 _ b 15 Ground Presence of changeover coil 2 wires Machine termina...

Page 16: ...ed out proceed with system start up for the unit checking the steps below For units with DX coil the refrigerating machine must be operational system start up of the refrigerating machine not provided...

Page 17: ...g this period Maintenance intervals The filter life depends essentially on the amount of dust in the air and the efficiency of the filtration system The filtration quality cannot be maintained if the...

Page 18: ...en the door 2 Remove the upper and lower fixings from the electrics box 3 Move the electrics box a sufficient length of cable is provided 4 Disconnect the various quick connectors 5 Provide sufficient...

Page 19: ...etighten the connections twice a year Visually inspect the components wires and cables ELECTRIC HEATERS The electric heater requires very little maintenance However the following checks are necessary...

Page 20: ...ive detergent Refrigerant circuit if DX coil Refer to the instruction manual for the outdoor unit 8 TESTS AND GUARANTEES To guarantee the product s quality each air handling unit undergoes a variety o...

Page 21: ...EN EN 21...

Page 22: ...EN 22...

Page 23: ...EN EN 23...

Page 24: ...ndustrielle d Applications Thermiques Corporation with a capital of 26 728 480 Bourg en Bresse Register of Trade and Companies no B 545 620 114 Non contractual document As part of our continuous drive...

Reviews: