<Notes>
• Please do not let any type of gas other than the specified refrigerant go into the refrigeration system;
• In case of refrigerant leakage during operation, please replace the gas. (Fill the refrigerant at the outdoor unit)
Paste the refrigerant oil here
Torque spanner
Spanner
Pipe joint
Cone nut
Fig.1
Select piping material
• Make sure both the internal surface and external surface of the pipes are intact and are free from harmful
contaminants such as sulphur, oxide, foreign matter, cutting powder, grease and water.
• Please use the following materials for refrigerant pipe.
connection kit
AH1-280A AH1-560A
Connection kit-indoor max. single pipe length /m
5
5
Connection kit- indoor max. drop /m
5
5
Connection kit- electrical box max. distance
5
5
• The branching pipe for the pipe must have refrigerant branching suite. For selection of refrigerant branching
suite and max. height drop between indoor units, please refer to the installation instructions or technical data
attached to the outdoor unit.
Outdoor
Connection Kit
Connection Kit
Indoor
Electrical box
Max. length 5m
Max. length 5m
The high-pressure gas pipe, suction gas pipe, liquid pipe must be provided
with reliable thermal insulation. In the absence of thermal insulation, liquid
leakage may happen.
The outdoor unit is already filled with refrigerant.
To connect the pipes to connection kit or remove them from connection kit,
do use both spanner and torque wrench, as shown in the Fig.1.
Apply refrigerant oil to inside and outside of the flare. Screw it for 3 to 4
rounds with hands and then tighten it.
Determine the tightening torque. (Excessive tightening may damage the nuts
and hence cause leakage)
Check the connecting pipes for gas leakage and then fix the thermal
insulation, as shown in the in the Fig.2
Only use sealing gasket to wrap the part jointing between the gas pipe and
thermal insulation.
For pipe cutter and flare tool, please use R410A special tools.
Indoor
Max. height drop 5m
Summary of Contents for CA43BV-V5J1H Series
Page 1: ...VERSION A DATA Aug 12th 2016 SEVICE MANUAL AHU VALVE BOX ...
Page 8: ...6 AH1 560A 13 59 161 266 296 309 433 501 597 553 14 84 78 87 192 201 99 266 193 12 39 83 9 ...
Page 28: ...26 6 PCB photo 0151800113A SW01 SW03 SW07 LED7 LED3 LED4 LED2 LED1 LED5 ...
Page 43: ...CARRIER INTERAMERICA CORPORATION MIAMI FLORIDA USA C CIAC 2016 ...