20
Selection of piping dimensions
Select refrigerant branching dimensions between outdoor units and connection kit, between connection kit and
indoor units according to the Operation & Installation Manual of outdoor units and indoor units.
Dimensions (mm) of connection pipe of the vale box
model
Dimension
(
outer diameter
)
Gas pipe/ convertible dimension Liquid pipe/ convertible dimension
AH1-280A
Ø25.4/Ø22.22/Ø19.05
Ø9.52/Ø12.7
AH1-560A
Ø28.58/Ø25.4/Ø22.22
Ø9.52/Ø12.7
Nitrogen cylinder
Refrigerant pipe
Nitrogen
Nitrogen
Weld
Binding
<Note>
• For pipe welding, do not use antioxidant, for its residue may cause tube blocking and component fault.
• For pipe welding, do not use flux. If the flux is chlorine product, it will corrode the tube; if it contains fluorine, it will
even cause detrimental effects to the refrigerant system, such as refrigerant oil deterioration. Please do not use
phosphor copper for welding material (BCup-2).
<Note>
• Excessive tightening will result in cracking at the flare and refrigerant leakage.
• To weld the refrigerant pipe, please make nitrogen replacement (*1), or send nitrogen (*2) into the refrigerant pipe
while welding the pipe (refer to Fig.3). Finally use the flare or flange to connect the indoor unit and connection
kit.
(*1) Nitrogen replacement method is provided in the multi-split system work manual.
(*2) If nitrogen flowing and welding proceed simultaneously, do use pressure reducing valve. Approximately 0.02
MPa (0.2 Kg/cm with a slight feeling of breeze) pressure is quite proper.
<Table-2>
Pipe size Tightening angle Recommended tool length
(mm)
Ø6.35
60°~90°
150
Ø9.52
60°~90°
200
Ø12.7
30°~60°
250
Ø15.88
30°~60°
300
Ø19.05
20°~35°
450
Apply refrigerant oil
Summary of Contents for CA43BV-V5J1H Series
Page 1: ...VERSION A DATA Aug 12th 2016 SEVICE MANUAL AHU VALVE BOX ...
Page 8: ...6 AH1 560A 13 59 161 266 296 309 433 501 597 553 14 84 78 87 192 201 99 266 193 12 39 83 9 ...
Page 28: ...26 6 PCB photo 0151800113A SW01 SW03 SW07 LED7 LED3 LED4 LED2 LED1 LED5 ...
Page 43: ...CARRIER INTERAMERICA CORPORATION MIAMI FLORIDA USA C CIAC 2016 ...