Chapter 6 Detailed function description
-100-
F1.05 Stop mode
Setting range :0
~
1 Factory setting: 0
0
:
Ramp to stop
When the stop command takes affect. The inverter decreases the output
frequency according to the selected acceleration/deceleration time till stop.
1
:
Coast/Free stop
When the stop command takes affect,the inverter blocks the output immediately.
the motor coasts to stop by its mechanical inertia .
F1.06 Starting frequency of DC braking at stopping
Setting range:0.00
~
F0.04
Factory setting:0.00Hz
F1.07 Braking wait time at stopping
Setting range: 0.0
~
50.0s
Factory setting:0.0s
F1.08 DC braking current at stopping
Setting range: 0.0
~
150.0%
Factory setting:0.0%
F1.09 DC braking time at stopping
Setting range: 0.0
~
50.0s
Factory setting:0.0s
F1.06 The frequency of DC braking starting when the inverter is decelerating
to stop .
F1.07 The inverter close output for an interval and then braking befor DC
braking .
F1.08 The percentage of rated current of inverter. The bigger the DC braking
current .the greater the braking torque .
F1.09 The maintain time for DC braking at stopping .
Summary of Contents for ZVF300H
Page 2: ......
Page 3: ...Software Version V3 75 Printing Date 2020 09 ZVF300H ZVF300H ...
Page 4: ...P1 P8 P1 P2 P2 P3 P5 P8 P9 P17 P9 P9 P9 P10 P13 P15 P18 P38 P18 P19 P24 P35 P39 P42 P39 ...
Page 6: ......
Page 7: ......
Page 8: ......
Page 9: ...method ...
Page 10: ...not personnal ...
Page 11: ...suitable ...
Page 12: ......
Page 13: ...Figure 1 5 Three phase AC Power supply ...
Page 15: ...Board ...
Page 16: ...Board ...
Page 17: ...3 Cabinet Body 8 The door of cabinet Board ...
Page 21: ...150 600 50 ...
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ...2 ...
Page 28: ......
Page 31: ......
Page 32: ......
Page 33: ...Applicable to model ZVF300H G0R4T2 3R7T2 ZVF300H G0R7T4 7R5T4 ZVF300H P4R0T4 011T4 ZVF300H ...
Page 41: ......
Page 44: ...ZVF300H ZVF300H ...
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ...till ...
Page 49: ...ZVF300H ...
Page 50: ...AO1 ...
Page 51: ...AO1 ...
Page 52: ...AO1 15 ...
Page 53: ...AO1 ...
Page 176: ... 171 ...
Page 177: ... 172 ...
Page 178: ... 173 ...
Page 179: ... 174 ...
Page 180: ... 175 ...
Page 181: ... 176 ...
Page 182: ... 177 ...
Page 183: ... 178 ...
Page 184: ... 179 ...
Page 185: ... 180 ...
Page 186: ... 181 ...
Page 191: ... 186 ...
Page 192: ... 187 ZVF300H G132 P160T4 ...
Page 195: ... 190 ...
Page 196: ... 191 ...
Page 197: ... 192 ...
Page 198: ... 193 ...
Page 199: ... 194 ...
Page 200: ... 195 ...
Page 201: ... 196 ...
Page 202: ... 197 ...
Page 205: ... 200 8 E 1 8 O 1 Communication data structures Communication data format box ASCII mode ...
Page 208: ... 203 RTU mode ...
Page 211: ... 206 ...
Page 214: ... 209 3 6 The definition of communication of Parameter address ...
Page 215: ... 210 Table 3 1 Table 3 2 ...
Page 216: ... 211 Appendix Table 3 1 Data and fault type in 5000H ...
Page 218: ... 213 Appendix Table 3 2 Data and fault type in 5001H ...
Page 219: ... 214 ...