8. Tunnel Inlet Static Pressure assist in Power
If in the Power Mode, there is inadequate inlet area
to keep the static pressure within the high control
limits, the Tunnel Curtain will open to give addition-
al air inlet area. The Inlets are given continuous open
signals as the Tunnel Curtain takes over the respon-
sibility of controlling the static pressure. The static
pressure has to be above the high Static Pressure
Control limit continuously for one minute with 3 or
more Fans running for this to happen. Responsibility
for Static Pressure Control is passed back to the In-
lets as soon as there are fewer than 3 Fans running or
the Tunnel Curtain cannot bring the static pressure
back into the control range (while closing) from the
low side. The static pressure has to be below the low Static Pressure Control limit continuously for
one minute for this to happen.
Select the Back button twice after the Static pressure has been assigned and Control screen is com-
pleted
Control Setup
Chore-Tronics® 3 Control
26
MT2398C
Analog Inputs-Relative Humidity Sensor
1. House Relative humidity Sensor
From the Setup/Analog Input screen select House
RH sensor Button.
2.
Assign the House RH sensor input as you did
the House Sensors. Calibration is also done from
this screen. See next manual section "Calibrating
Analog Inputs".
Summary of Contents for Chore-Tronics 3 Control
Page 1: ...Chore Tronics 3 Control Installation Operator s Instruction Manual MT2398C November 2013...
Page 124: ...Wiring Diagrams Chore Tronics 3 Control 124 MT2398C Fan Wiring Figure 45 Fan Wiring...
Page 127: ...Chore Tronics 3 Control Wiring Diagrams MT2398C 127 This page left blank intentionally...
Page 128: ...Wiring Diagrams Chore Tronics 3 Control 128 MT2398C Brooder Wiring...
Page 129: ...Chore Tronics 3 Control Wiring Diagrams MT2398C 129...