Chore-Time 49000-4 Installation And Operator'S Manual Download Page 11

PDS™ Control 4 and 8 Station

Operation

MW1402D

11

Adjusting the water column height in the individual stand 
tubes. To adjust the water column height turn the red 
adjustment knob counter-clockwise to increase and clock-wise 
to decrease 

(see figure 10.) 

until the water column gauge reads 

the desired water column height. 

Note: Individual PDS Volumatic regulators provide a 

minimum water column height in 
case air pressure is lost. The 
regulators CAN NOT be adjusted 
below this height regardless of the 
water column gauge reading.

Refer to the Rain Bird Timer manual for specific programing details.

The Rain Bird Timer has the capacity to 
have three individual programs: "A", "B", 
and "C".

Single stations or all stations may be 
manually flushed at any time. Refer to 

Operating the Sprinkler Timer 

section in 

the Rain Bird manual.

When birds go out it is a good idea to turn 
the Rain Bird Timer to the off position and 
turn the adjustment knob on the PDS control 
to the minimum setting.

Each program can have up to four daily start 
times. As long as there are start times 
entered for stations in a particular program 
that program will run. To maintain multiple 
programs in the control without all of them 
running, all the start times in the undesired 
programs must be set to off. The unused 
programs (except the start times) are retained but will not run until the start times are re-entered. This allows you 
to program one, two or three separate flushing sequences. For example, one for summer and one for winter or one 
for brooding and one for finishing.

Each station can be set to run from a minimum of 0 minutes to a maximum of 4 hours in 1 minute intervals. The 
actual amount of time it takes to completely change the water in a 3/4" drinker line is dependent on the flow rate 
through the line. This flow rate can easily be estimated by putting the regulator into flush and timing how long it 
takes to fill a container of known volume at the drain end of the line. Once this time is determined use the formula 
below to calculate the flow rate in gallons or liters per minute and then refer to the charts 

on page 12

 to determine 

the estimated flush time in minutes for your specific line length. 

For example, if it takes 185 seconds to fill a 5 gallon container the resulting flow rate would be 1.6 GMP.

Operation

Flushing The System

Volume of Container (Gallons or Liters)

=

Flow Rate in Gallons or Liters per Minute

Seconds to Fill Container Divided by 60

5 Gallons

=

5

=

1.6 Gallons per Minute.

185/60

3.08

Figure 10. Adjusting the water column

Figure 11. Operating the control

Summary of Contents for 49000-4

Page 1: ...PDS Control 4 and 8 Station Pneumatic Drinking System Installation and Operators Manual MW1402D August 2008...

Page 2: ...considered defects under the Warranty 5 This Warranty applies only to systems for the care of poultry and livestock Other applications in industry or commerce are not covered by this Warranty Chore Ti...

Page 3: ...ultiple House Layout 6 Installation 7 Wiring 7 CHORE TRONICS 7 Tubing 9 Compressed Air Supply 9 Water Column Gauge Calibration 10 Air Leak Test 10 Operation 11 Flushing The System 11 Flushing Recommen...

Page 4: ...ntent that is different from the authoritative CTB published English version of the manual For current product installation and operation information please contact the customer service and or technic...

Page 5: ...t for any other purpose or in a way not within the operating recommendations specified in this manual will void the warranty and may cause personal injury This manual is designed to provide comprehens...

Page 6: ...talling the PDS system Refer to Parts List Section page 15 for item part numbers Broiler System Layout Figure 1 Broiler Layout Multiple House Layout Figure 2 4 House Layout Air can be run from a centr...

Page 7: ...rol is still disconnected and no backup battery is installed All wiring must be done by a qualified electrician in accordance with local and national codes CHORE TRONICS When using CHORE TRONICS to mo...

Page 8: ...tation 8 MW1402D Figure 4 Rain Bird Chore Tronics Wiring Figure 5 Internal Wiring OPTIONAL SECOND I O BOARD MODEL 32 40 ONLY CHORE TRONICS CONTROL 24VAC COIL RELAY NOT SUPPLIED Rain Bird Timer 8 7 6 5...

Page 9: ...regulator with 1 4 fitting and has adjustable range of 0 125 psi Approved air regulators Grainger Industrial Supply Part number 4ZMO8 Grainger Industrial Supply Part number 4ZMO6 NAPA Part number 90...

Page 10: ...he water column gauge remove the plastic cover with a small screwdriver Then turn the calibration screw see figure 9 until the gauge reads the correct water column height Replace the plastic cover on...

Page 11: ...all of them running all the start times in the undesired programs must be set to off The unused programs except the start times are retained but will not run until the start times are re entered This...

Page 12: ...s TotalLine Capacity 17 0 Gallons TotalLine Capacity 20 4 Gallons TotalLine Capacity 23 8 Gallons TotalLine Capacity 27 2 Gallons Gallons of water in one foot of 3 4 Chore Time water pipe 034 Water Li...

Page 13: ...often until these problems disappear The sediments could react with medications vaccines and electrolytes They will also hamper the effects of disinfectants and cleaners chlorine and acids Flushing Af...

Page 14: ...air source and that house 2 With the incoming air off and the gauge indicates that there is a 2 PSI drop or more within 1 minute the problem is in the control lines or regulators 3 Shut off or pinch o...

Page 15: ...19 Control Decal 2529 883 2529 883 7 Control Box Latch Pivot 30863 30863 20 Pigtail Connector 5907 1 5907 1 8 Airloader W Adjustment Knob 48837 48584 21 120V Timer Control 50819 1 50819 2 9 1 4 OD 1...

Page 16: ...ore Time distributor or representative for additional parts and information CTB Inc P O Box 2000 Milford Indiana 46542 2000 U S A Phone 574 658 4101 Fax 877 730 8825 E mail poultry choretime com Inter...

Reviews: