25
Step 1
Remove an appropriate length of the insulation layer from the positive and negative
power cables by using a wire stripper, as shown in Figure 5.9.
Positive metal connector
Figure 5.9 Removing insulation layer for DC cable (unit: mm)
Negative metal connector
Step 2
Insert the exposed areas of the positive and negative power cables into the metal
terminals of the positive and negative connectors respectively and crimp them using a crimping
tool, as shown in Figure 5.10.
Figure 5.10 Crimping a metal connector
Step 3
Insert the crimped positive and negative power cables into the corresponding positive
and negative connectors until a "click" sound is heard, as shown in Figure 5.11.
Figure 5.11 Connecting positive and negative connectors
PC
CPS SCA-
T Series Inverter
5
.
3
.
2 Procedures of Connecting the PV Strings