NOTE
It is recommended that the ground cable be connected to a nearby
ground position. For a system with multiple inverters connected in
parallel, connect the ground points of all inverters to ensure
equipotential connections.
Step 1
Remove an appropriate length of the insulation layer from the PGND cable using a wire
Stripper; the length should be 2mm~3mm longer than OT terminal’s crimping end, as shown in
Figure 5.1.
Figure 5.1 Stripped length (unit: mm)
Step 2
Insert the exposed core wires into the crimping areas of the OT terminal and crimp them
using hydraulic pliers, as shown in Figure 5.2.
Figure 5.2 Crimping a cable (unit: mm)
19
CPS SCA-
T Series Inverter
5.1.2 Wiring Procedures
Specification
:
OT35~50-6
Step 3
Remove the ground screws from the ground points, secure the PGND cable (done by
step 1 & 2) using the ground bolts, and tighten the bolts to a torque of 5 N•m using a socket
wrench, as shown in Figure 5.3. PE wire must be well grounded to ensure that impedance
between Neutral wire and Earth wire be less than 10Ω.
Figure 5.3 Securing the PGND cable