40
UK
Chloride Active
945044.066
8.1.2 Battery Packs
BP-A1000/1500-T
BP-A1000/1500-RT
BP-A2000/3000-RT
Housing
Tower
Rack/Tower
Rack/Tower
Battery arrangement
2x3x7,2Ah
2x3x7,2Ah
2x6x9Ah
Protection
Breaker 70A/80Vdc
Breaker 70A/80Vdc
Breaker 70A/80Vdc
MECHANICAL
Size (WxHxD, mm)
157x245x438
438x86(2U)x438
438x86(2U)x657
Weight (kg)
20
32
52
ENVIRONMENTAL
Operating temperature
0 - 40 ºC
Storage temperature
-15 ºC / +40 ºC
Altitude
0-3000m
Relative humidity
10% to 90%
8.2 Runtime charts
Theoretical values with fully charged batteries and resistive load.
NOTE:
The maximum quantity of external battery packs that can be connected to the UPS is four.
Active 700 T:
Load
UPS
UPS
+ 1 BP
UPS
+ 2 BP
UPS
+ 3 BP
UPS
+ 4 BP
80W
63 min
239 min
438 min
661 min
861 min
160W
37 min
158 min
254 min
397 min
476 min
240W
26 min
91 min
197 min
262 min
372 min
320W
20 min
69 min
145 min
212 min
263 min
400W
15 min
55 min
97 min
174 min
220 min
480W
13 min
45 min
80 min
136 min
191 min
560W
11 min
38 min
69 min
99 min
161 min
640W
9 min
33 min
60 min
86 min
130 min
720W
7 min
29 min
51 min
75 min
99 min
800W
6 min
25 min
46 min
67 min
89 min
Active 1000 T and Active 1000 RT:
Load
UPS
55W
51 min.
110W
35 min.
170W
24 min.
225W
18 min.
280W
15 min.
335W
12 min.
390W
10 min.
450W
8 min.
505W
7 min.
560W
5 min.