Chloride Active
945044.066
4.2.2.2 Warning and fault indicators
The LCD Display shows the last ve events stored and the runtime when they happened (menu 4). They
are listed from 1 to 5, being 1 the newest event and 5 the oldest event. Event 1 is the rst one to be
displayed and events from 2 to 5 are displayed sequentially by pressing the Scroll-Down button.
4.3 Rear Side
4.3.1 Tower units
Active 700 T:
Display Message
Description
RPO ACTIVE
UPS stopped because RPO (Remote Power Off) has been activated
BATTERY FAULT
Battery failure has been detected. Please check batteries.
INVERTER OVERLOAD
Overload detected on the inverter (line mode or battery mode)
BYPASS OVERLOAD
Overload detected when the unit is on bypass mode
FAN FAULT
Fan failure has been detected
CHARGER OVERVOLTAGE
Charger is delivering overvoltage (internal failure)
DC BUS OVERVOLTAGE
DC voltage on the DC bus too high (internal failure)
DC BUS UNDERVOLTAGE
DC voltage on the DC bus too low (internal failure)
DC BUS UNBALANCE
DC voltage on the DC bus unbalanced (internal failure)
INVERTER OVERVOLTAGE
Inverter is delivering overvoltage (internal failure)
INVERTER UNDERVOLTAGE
Inverter is delivering undervoltage (internal failure)
INVERTER SHORT
Short-circuit on the inverter (internal failure)
SITE WIR. FAULT
Site wiring fault detected. Please check input wiring arrangement.
1. SNMP Slot
2. Input circuit breaker
3. Input power connection
4. Not controllable output sockets
5. Controllable outlets (2 groups)
6. USB port
7. RS232 port
8. Fan
9. ROO/RPO terminals
10. Earth screw