48
Table 1 Continued - Input/ Output Ratings & External Wiring Recommendations
Nom output current ( 3Ph, 1 Neutral, 1 gnd)
A AC
347
416
Minimum conductor size (number per phase)
AWG or
kcmil 250(2) 350(2)
208V-208Y/120
Recommended output circuit breaker ratings
3 Pole, A
AC 450 600
Nom output current ( 3Ph, 1 Neutral, 1 gnd)
A AC
347
416
Minimum conductor size (number per phase)
AWG or
kcmil 250(2) 350(2)
480V-208Y/120
Recommended output circuit breaker ratings
3 Pole, A
AC
450 600
Nom output current (3Ph, 1 Neutral*, 1 gnd)
A AC
150
180
Minimum conductor size (number per phase)
AWG or
kcmil
4/0 300
AC Out
put
to
Cr
itical L
o
ad
480V - 480V
Recommended output circuit breaker ratings
3 Pole, A
AC
200 225
Battery Current at end of discharge
A DC @
396V 309 370
DC In
put
480V DC
Minimum conductor size (number per pole)
AWG or
kcmil 3/0(2) 4/0(2)
Refer to the following notes when planning your installation.
1) Wire sizes, ratings and circuit breaker sizes are recommended, always consult NEC codes.
2) Consult Local and National electrical codes for acceptable wiring practices.
3) Wires specified are Copper type 75 Deg C / 167 Deg F rated, based on ambient temperature of 104 Deg F.
4) Neutral conductors are considered to be current carrying conductors. Refer to the NEC tables and notes for neutral conductors,
And grounding system requirements. Chloride recommends neutral to be 2x phase conductor.
5) We recommend that the wire size, ratings and circuit breakers be sized to the maximum kVA rating to allow for future up-grades.
6) *AC Input to Bypass requires Neutral if Load requires Neutral.
7) Max currents include Nominal currents plus battery recharge and are not considered continuous.