Chapter 5 Functional Parameter Simple List 200 Series General Purpose Vector AC Drive
54
Hundred: Input phase loss protection
0: Invalid 1: Valid
Thousands : Output loss-Phase protection
0: Invalid 1: Valid
Fb-01
Continuous failure rest
time
1.0
~
600.0s
30.0s
√
Fb-02
Motor overload
protection point
20.0
~
125.0%(motor rated current)
100.0%
√
Fb-03
Bus overvoltage stall
protection point
115
~
150%
The larger the value, the stronger the ability to
suppress overvoltage, but the actual
deceleration time will be longer. Under the
premise of no overvoltage, for the gain setting,
the smaller , the better.
133%
√
Fb-04
Over current speed loss
protection point
10.0
~
210.0%(Motor rated current)
During the acceleration and deceleration of the
drive, when the output current exceeds the
over-current stall protection current, the drive
stops the acceleration and deceleration process,
and continues to accelerate and decelerate after
the output current drops.
180.0%
√
*
Fb-05
Frequency decrease rate
in current limiting
0.00
~
50.00Hz/s(Controlled by Fb-19)
2.50Hz/s
√
Fb-06 Auto reset times
0
~
20
0
√
Fb-07
Fault automatic reset
interval time set
0.100
~
32.000s
1.000s
√
Fb-08 First two failure types
E000: No faulty
E001: IGBT shorted protection
E003: Overvoltage in stop
E004: Over-current in accelerating
E005: Over-current in decelerating
E006: Over-current in constant-speed running
E007: Over-voltage in accelerating
E008: Over-voltage in decelerating
E009: Overvoltage in constant-speed running
E010: DC Bus low-voltage fault
E011: Motor overload
E012: AC Drive overload
E013: Input phase loss
E014: Output phase loss or unbalance current
E015: Terminal water lack input faulty
E016: IGBT module overheat fault
E017: External fault
0
○
Fb-09 Latest fault type
0
○
Fb-10 Present fault type
0
○