200 Series General Purpose Vector AC Drive Chapter 5 Functional Parameter Simple List
35
rotation, three-wire terminal is normally open,
and stops when closed.
F0-14
Motor control mode
(it needs to set F0-14=0
、
F0-28=1 when torque
control)
0: No PG speed vector control(needs to set F3
group motor parameters and perform parameter
auto-learning)
1: VF control ( See F2 group VF parameters)
1 ×
F0-15 Model type selection
0: G Type(Constant torque load model)
1: P Type(Load models such as fans and pumps)
0 ×
F0-16 Motor rated voltage
10
~
1000V
380V ×
*
F0-17 Motor rated frequency
1.00
~
F0-05
50.00Hz
×
*
F0-18 Expansion cards type
0: No expansion cards
1: Isolated communication card (welding
RGLK resistance, remove the U8 and RGLK
resistors on main board)
2: IO card (welding RKZK resistance, remove
RGLK resistors)
3: Injection card (welding RKZK resistance,
remove RGLK resistors)
0 ×
F0-19 UP/DOWN
setting
0: Zero clearing when stop
1: Without zero clearing when stop
1
√
F0-20 UP/DOWN
change
rate
0.01
~
100.00Hz/s
2.00Hz/s
√
F0-21
Modulation function
selection
Unit : VF automatic stable voltage
Decade: VC automatic stable voltage
0: Invalid
1: Valid for whole process
2: Invalid only when decelerating
Hundred: PWM selection
0: Asynchronous modulation
1: Synchronous modulation
0000
√
F0-22 Carrier
frequency
0.600
~
16.000 kHz(The maximum carrier is
related to the model) By increasing the carrier
frequency, the noise of the motor can be
reduced, and the leakage current of the line to
the ground can be reduced. But it will increase
the heating and affect the life of the ac drive.
Model
depends
√
F0-23
Voltage of energy
consumption brake valve
110
~
150%(standard busbar voltage)
220V series,100% corresponds to 311V
380V series,100% corresponds to 537V
690V series , 100%corresponds to975V
123%
√
F0-24
Frequency is less than
frequency lower Limit
selection
0: Run at lower limit frequency (F0-07)
1: Run at zero frequency (With output voltage,
controlled by F2-01 torque boost)
0
√