19
-
4) Connection of High order communication RS-485
The RS-485 communications interface is connected to a personal computer via a protocol converter (our
Model SC8-10: sold separately). Three signals of SD, RD and SG are used between the protocol
converter and a personal computer and a control signal is not used. Wiring process of connector similar
to “(3) High order communication RS-232” on the previous page, is necessary.
High order communication for RS485
To ensure the transmission of data via RS-232C or RS-485 communications, mount a termination resistor
at both ends of transmission lines. When the protocol converter (SC-8) is at an end of a transmission
circuit, short the terminals of
4
and
5
of the unit to insert the termination resistor automatically.
Mounting termination resistor
Notes
SA
232+485
485+485
PC
(9-pin or 25-pin)
KR2000 series
graphic recorder
1
SA2
SB2
SG
RD
SD
SG
RDA
RDB
SDA
SDB
1
2
3
4
5
6
7
8
SA
SB
SG
SA
SB
SG
KR2000 series
graphic recorder 2
KR2000 series
graphic recorder 3
Protocol converter
(SC8-10)
Within 15m
Within a total length of 1.2Km (max 31 set)
Termination resistor
100
Ω
1/4W
The above figure
shows an example
of 9 pin connector.
RD
SD
ER
SG
DR
RS
CS
2
3
4
5
6
7
8
Transmitting
data
SB
Received
data
Internal
circuit
For wiring process of connector, refer to “3) High order communication for
RS-232”.
Summary of Contents for KR2000
Page 27: ... 25 MEMO ...