Chiltrix Inc.
C28
Thermal switch status
1=on, 0= off
1=on, 0= off
C29
outdoor fan motor
1= run, 0= stop
1=on, 0= off
C30
electrical valve 1
1= run, 0= stop
1= run, 0= stop
C31
electrical valve 2
1= run, 0= stop
1= run, 0= stop
C32
electrical valve 3
1= run, 0= stop
1= run, 0= stop
C33
electrical valve 4
1= run, 0= stop
1= run, 0= stop
C34
C4water pump
1= run, 0= stop
1= run, 0= stop
C35
C5water pump
1= run, 0= stop
1= run, 0= stop
C36
C6water pump
1= run, 0= stop
1= run, 0= stop
C37
The accumulative days after last
virus killing
0-99 (From the last complete
sterilization to the present,
cumulative number of days
)
0-99 (from the last complete
sterilization to the present,
cumulative number of days)
C38
outdoor modular temp
-30~97
℃
-30~97
℃
C39
Expansion valve 1 opening degree
0~500
0~500
C40
Expansion valve 2 opening degree
0~500
0~500
C41
inner pipe temp display
-30~97
℃
-30~97
℃
C42
Heating
Method
2
target
temperature
-30~97
℃
-30~97
℃
C43
Indoor temperature control switch 1=on, 0= off
1=on, 0= off
C44
fan type
0= AC fan, 1= EC fan 1,
2= EC fan 2
0= AC fan, 1= EC fan 1,
2= EC fan 2
C45
EC fan motor 1 speed
0~3000
0~3000
C46
EC fan motor 2 speed
0~3000
0~3000
C47
water pump types
0= AC Water pump
1= EC Water pump
0= AC Water pump
1= EC Water pump
C48
water pump1 speed (C4)
1~10
(
10 Show 100%
)
1~10 (10 means 100%)
C49
water pump2 speed
1~10
(
10 Show 100%
)
1~10 (10 means 100%)
C50
Inductor AC Current value P15
0~50A
0~50A
C51
Driver working status value
Hexadecimal value
Hexadecimal values
C52
Compressor shut down Code
Hexadecimal value
Hexadecimal values
C53
Driver allowed highest frequency
30-120Hz
30-120Hz
C54
Reduce
frequency
temperature
setting
55~200
℃
55~200
℃
C55
input AC Voltage value
0~550V
0~550V
C56
input AC current value
0~50A
(
IPM test
)
0~50A
(
IPM Check
)
C57
Compressor phase current value
0~50A
(
IPM test
)
0~50A
(
IPM Check
)
C58
Bus line voltage
0~750V
0~750V
C59
Fan shutdown Code
Hexadecimal value
Hexadecimal values
C60
IPM temp
55~200
℃
55~200
℃
C61
Compressor total running time
Will reset after power cycle
0~65000
0~65000 hour
NOTE: Your controller will show some parameters that are not listed here,
If they are not listed they are not applicable to the CX34
52
Summary of Contents for CX34
Page 4: ...Chiltrix Inc www chiltrix com CX34 Components 4 ...
Page 17: ...Chiltrix Inc www chiltrix com Electric Connections and Component Locator 17 ...
Page 18: ...Chiltrix Inc www chiltrix com CX34 System Wiring Diagram 18 ...
Page 24: ...Chiltrix Inc www chiltrix com G3 VALVE Seasonal Switch Valve G3 Ports 24 ...
Page 41: ...Chiltrix Inc www chiltrix com Standard Controller cont d Timer 4 Mode settings 41 ...