Chiltrix Inc.
4. Parameter Checking and Setting “MFG MODE”
NO Name
scope/means
Range, Meaning
Default
P00 Power-down recovery function
0
:
off
;
1
:
on
0
:
off
;
1
:
on
1
P01 Input Power:
Single / three phase selection
0
:
Single-phase 1
:
Three-phase
0
:
Single-phase power Three-
phase power
0
P02 Power frequency
0
:
50HZ
;
1
:
60HZ
5
:
50HZ
;
1
:
60HZ
1
P03 Heat source selection
0
:
ground source
;
1
:
air source 0
;
ground source
1
:
Air source
1
P04 Heating temperature control
method
0
:
Method 1
;
1
:
Method 2
0
:
Method 1 : 1
:
Method 2
0
P05 Defrost method selection
0
:
Method 1
;
1
:
Method 2
0
:
Method 1 : 1
:
Method 2
0
P06 FREECOOLING validation
0
:
valid
;
1
:
invalid
0
:
valid
;
1
:
invalid
1
P07 Frequency control method
0
:
Method 1
;
1
:
Method 2
0
:
Method 1
;
1
:
Method 2
0
P08 DHW validation G1
0
:
valid
;
1
:
invalid
0
:
valid
;
1
:
invalid
1
P09 Air conditioning and heating
validation
0
:
valid
;
1
:
invalid
0
:
valid
;
1
:
invalid
0
P10 Air conditioning and Cooling
validation
0
:
valid
;
1
:
invalid
0
:
valid
;
1
:
invalid
0
P11 DHW hot water temp hysteresis
2
~
15
℃
,
minus hysteresis
2
~
15
℃
,
minus hysteresis
2
℃
P12 AC temp hysteresis
2
~
15
℃
,
minus hysteresis
2
~
15
℃
,
minus hysteresis
2
℃
P30 fan motor Category
0=AC fan, 1=EC fan1, 2=EC fan 2
0=AC Fan, 1=EC Fan1, 2= EC
1
P31 Maximum speed of the fan
10-100
(
100 show1 00%
)
1-10
(
10=100%
)
100
P32 Heating fan speed control
temperature difference
2
~
15
℃
2
~
15
℃
6
℃
P33 Cooling Fan speed control
Temperature difference
5
~
18
℃
5
~
18
℃
12
℃
P34 Defrost method
0
:
Method 1
;
0
:
Method 1
;
0
P35 defrost starting temp
-5~5
℃
C00 Pipe sensor
-1
℃
P36 defrost interval time multiple rate 0
:
Not defrost
;
1
;
2
;
3
;
4
:
(
interval X 4
)
0
:
Not defrost
;
1
;
2
;
3
;
4
:
(
interval X 4
)
1
P37 The first defrost interval
15~99minu
(
1st interval after
repower on
)
15~99minute
(
1st interval after
repower on
)
35
P38 defrost exit temp
10~35
℃
C00 Pipe sensor
30
℃
P45
Allowed defrost coil temperature
-20~5
℃
Defrost method 1 Condition 2
-6
℃
NOTE: Your controller will show some parameters that are not listed here,
If they are not listed they are not applicable to the CX34
47
Summary of Contents for CX34
Page 4: ...Chiltrix Inc www chiltrix com CX34 Components 4 ...
Page 17: ...Chiltrix Inc www chiltrix com Electric Connections and Component Locator 17 ...
Page 18: ...Chiltrix Inc www chiltrix com CX34 System Wiring Diagram 18 ...
Page 24: ...Chiltrix Inc www chiltrix com G3 VALVE Seasonal Switch Valve G3 Ports 24 ...
Page 41: ...Chiltrix Inc www chiltrix com Standard Controller cont d Timer 4 Mode settings 41 ...