Electric connection
General
Note!
Electrical installation and service must be carried out under the supervision of a qualified electrician.
Electrical installation and wiring must be carried out in accordance with the NEC.
The heat pump must not be connected without the permission of the electricity supplier and must be
connected under the supervision of a qualified electrician. Wires, spare parts and materials etc. must
satisfy the relevant standards issued by the host country or region.
The heat pump does not include an AC disconnect or switch on the incoming electrical supply. The power
supply cable must be connected to a circuit-breaker with at least a 3 mm breaking gap. Incoming supply
must comply with the technical requirements, with a frame ground wire (neutral is not used), via a
distribution box with breakers.
Voltage range is 208-240vac
Maximum current draw is 13 amps, minimum wire size is 12 AWG, minimum breaker size is 20 AMP.
Main terminal block inside electronics box