Second Heat Source or Assistant Electric Heater
Parameter 27, 28 usage
If you set parameter 27 to "0", E2 is the assistant electric heater control port, if
you set parameter 27 to 1, E2 will be 2nd heat source control port. If the E2 port is the assistant electric
heater control port, it is controlled by parameter 10. If air temp < Parameter 10, E2 will be active. But it
will not start at once, if the compressor cannot reach target temp within 15 minutes, it will energize the
relay coil at E1& E2. The compressor will work together with E2. If E2 is 2nd heat source control port, it is
controlled by parameter 28. When air temp is lower than parameter 28 (default -15c), E2 will be energized
and the compressor will stop. Only the 2nd heat source is working with E2. You can connect the electric
boiler on/off signal to E2. E2 only provides an "on/off" signal. You can connect your own controls, it's max
current is 1 amp. You must add a relay to protect the heat pump PCB, so if there are any problems from
the electric boiler, it will not damage the heat pump PCB. If your winter is not too cold (above -15c), you
can use E2 as an assistant electric heater. If your winter is too cold, (lower than -18c~-20c), the compressor
will work too hard, so you should set E2 as 2nd heat source port to protect the heat pump.
Summary of Contents for AC series Heating & Cooling series CX30
Page 4: ...Chiltrix Inc www Chiltrix com 4 Components ...
Page 10: ...Chiltrix Inc www Chiltrix com 10 Freeze protection ...
Page 15: ...Chiltrix Inc www Chiltrix com 15 Clearances unit mm 200mm 8 350mm 14 400 16 500 20 1000 40 ...
Page 24: ...Chiltrix Inc www Chiltrix com 24 G1 Valve Wiring and Parameters ...
Page 27: ...Chiltrix Inc www Chiltrix com 27 G3 VALVE Seasonal Switch Valve Solar Preheat Valve ...