Chiltrix Inc.
www.Chiltrix.com
48
P2 Low pressure
protection
Flash’s 9
times
1.
Low pressure switch
loose or faulty.
2.
Throttling device
(expansion valve)
problem
3.
Heat expansion valve
needs to be
preheated.
4.
Refrigerant low (leaks)
1.
If the error displays before
the compressor starts, it
means low pressure switch
error. Please reconnect the
low pressure switch or change
it.
2.
Open the thermostatic
expansion valve 360~180°.
3.
Disconnect the power for 3
minutes, connect power again
and turn on the unit. Repeat
this 2 or 3 times to preheat
the expansion valve.
4.
Check for refrigerant leakage.
P5
outdoor unit
water flow
fault
No flash
1.
Low water flow.
2.
Water flow switch
fault.
1.
Clean the water filter, check
water pump flow.
2.
Check and reconnect water flow
switch.
P6 outdoor unit
(water source
side) water
flow fault
Flash’s
17
times
1.
Water source side
water flow too small.
2.
Water flow switch
fault.
1.
Clean the water filter, check
water pump flow. Test the water
flow switch.
P7 phase loss
Flash
Power connection fault
Reconnect power supply wires
P8
Flash
Power connection fault
Reconnect power supply wires
P9
Flash
Power supply connection
fault or communication
between refrigeration pcb
and water control pcb.
1.
Check the power supply
wire connection and wires
between IPM pcb and the
Refrigeration pcb.
2.
Check the water control
PCB for loose connections.
Summary of Contents for AC series Heating & Cooling series CX30
Page 4: ...Chiltrix Inc www Chiltrix com 4 Components ...
Page 10: ...Chiltrix Inc www Chiltrix com 10 Freeze protection ...
Page 15: ...Chiltrix Inc www Chiltrix com 15 Clearances unit mm 200mm 8 350mm 14 400 16 500 20 1000 40 ...
Page 24: ...Chiltrix Inc www Chiltrix com 24 G1 Valve Wiring and Parameters ...
Page 27: ...Chiltrix Inc www Chiltrix com 27 G3 VALVE Seasonal Switch Valve Solar Preheat Valve ...