background image

Installation Instructions

EGX-SF2

7

Installing EGX-SF2

1.

Loosen two Phillips head screws holding EGX-SF2 outlet
box to outer housing. (See Figure 2)

2.

Rotate outlet box counter-clockwise until it is free to be
removed from housing. (See Figure 2)

3.

Remove outlet box from housing. (See Figure 2)

Figure 2

4.

Wire the EGX-SF2 outlet box as required. Refer to tables to
the right for input and output specifications. (See Figure 3)

CAUTION:

Isolated ground-mounting means NOT

grounded. Grounding wire connection required.

IMPORTANT ! :

If a separate isolated green/yellow

ground wire is installed in the building wiring, attach it
separately to the green/yellow isolated ground wire on
box. If there is no separate green/yellow isolated ground
wire, connect green ground wire to both green/yellow
isolated ground wire and green box ground wire on box.

NOTE:

The grounding conductors serving this outlet are to be
connected to earth ground at the service equipment or
other acceptable building earth ground such as the
building frame in the case of a high-rise steel-frame
structure. Connections should be made with minimum
AWG 14 copper wire intended for use on a 15 Amp
circuit. The conductors used to connect the outlet to the
line and to ground shall not be any longer than
necessary and shall avoid unnecessary bends.

NOTE:

An insulated grounding conductor that is identical in

size and insulation material and thickness to the
grounded and ungrounded circuit supply conductors,
except that it is green with or without one or more
yellow stripes, is to be installed as part of the circuit that
supplies the outlet. Refer to Table 250-122 of the
National Electrical Code regarding the appropriate size
of the grounding conductor.

NOTE:

Pressure terminal or pressure splicing connectors and
soldering lugs used in the installation of the outlet shall
be identified as being suitable for the material of the
conductors. Conductors of dissimilar metals shall not
be intermixed in a terminal or splicing connector where
physical contact occurs between dissimilar conductors
unless the device is identified for the purpose and
conditions of use.

1

x 2

2

2

3

outlet box

housing

Input

Input voltage, frequency

125 V AC, 60 Hz

Input connection type

4x14 AWG stranded, UL Style
1015, CSA TEW

Input Wire colors

Black - Line

White - Neutral

Green - Box Ground

Green/Yellow - Isolated Ground

Input wire length (ft.)

1 (with a 3/4” stripped end)

Output

Output

15 A, 1875 W

Power consumption

<0.5 watt

Fuses

Thermal current interrupting circuits
are in MOVs

Quantity/Type

Duplex NEMA 5-15R Isolated Ground
Receptacle

Color/Markings

Grey with protection symbol (Orange
triangle)

Figure 3

box ground wire

isolated ground wire

4

WHITE

(neutral)

GREEN

(box ground)

BLACK

(line)

GREEN/YELLOW

(isolated ground)

Summary of Contents for EGX-SF2

Page 1: ...truções de Instalação Istruzioni di installazione Installatie instructies Instructions d installation Power Conditioned Outlet Box Spanish Product Description German Product Description Portuguese Product Description Italian Product Description Dutch Product Description French Product Description EGX SF2 ...

Page 2: ... the installer s responsibility to make sure all components are properly assembled and installed using the instructions provided READ ALL INSTRUCTIONS BEFORE USING THIS PRODUCT DANGER TO REDUCE THE RISK OF ELECTRIC SHOCK 1 Always turn off power at source before installing the outlet WARNING TO REDUCE THE RISK OF BURNS FIRE ELECTRIC SHOCK OR INJURY TO PERSONS Always turn off power at source before ...

Page 3: ...are il fissaggio Bevestiging losdraaien Desserrez les fixations Phillips Screwdriver Destornillador Phillips Kreuzschlitzschraubendreher Chave de fendas Phillips Cacciavite a stella Kruiskopschroevendraaier Tournevis à pointe cruciforme Pencil Mark Marcar con lápiz Stiftmarkierung Marcar com lápis Segno a matita Potloodmerkteken Marquage au crayon Drill Hole Perforar Bohrloch Fazer furo Praticare ...

Page 4: ...EGX SF2 Installation Instructions 4 DIMENSIONS ...

Page 5: ...REQUIRED FOR INSTALLATION PARTS A 1 B 1 D 1 10 32 x 3 8 Earthing symbol IEC 60417 No 5019 affixed adjacent to grounding terminal Grounding screw and washer installed at factory Outlet box Outlet cover C 2 Clip E 1 New work clip F 2 12 24 x 3 8 ...

Page 6: ...t 1 Rule 10 906 Bonding conductor connection to circuits and equipment 6 A bonding jumper shall be installed to connect the bonding conductor to the grounding terminal of a receptacle and in such a manner that disconnection or removal of the receptacle will not interfere with or interrupt grounding continuity 7 In the case of metallically enclosed systems where the grounding path is provided by th...

Page 7: ...shall avoid unnecessary bends NOTE An insulated grounding conductor that is identical in size and insulation material and thickness to the grounded and ungrounded circuit supply conductors except that it is green with or without one or more yellow stripes is to be installed as part of the circuit that supplies the outlet Refer to Table 250 122 of the National Electrical Code regarding the appropri...

Page 8: ...t they are locked in place against the drywall and not laying flat against the EGX SF2 See Figure 7 Figure 7 11 Remove Phillips flat head screw and locking washer from in between outlets See Figure 7 12 Install faceplate B onto EGX SF2 using one Phillips flat head screw and locking washer removed in Step 11 See Figure 8 NOTE Make sure LED light on outlet box lines up with hole location on faceplat...

Page 9: ...n the building wiring attach it separately to the green yellow isolated ground wire on box If there is no separate green yellow isolated ground wire connect green ground wire to both green yellow isolated ground wire and green box ground wire on box NOTE The grounding conductors serving this outlet are to be connected to earth ground at the service equipment or other acceptable building earth grou...

Page 10: ...that it is locked in place against the drywall and not laying flat against the EGX SF2 See Figure 14 13 Remove Phillips flat head screw and locking washer from in between outlets See Figure 15 Figure 15 14 Install faceplate B onto EGX SF2 using one Phillips flat head screw and locking washer removed in Step 5 See Figure 16 NOTE Make sure LED light on outlet box lines up with hole location on facep...

Page 11: ...Installation Instructions EGX SF2 11 ...

Page 12: ...e com 08 17 USA International A 6436 City West Parkway Eden Prairie MN 55344 P 800 582 6480 952 225 6000 F 877 894 6918 952 894 6918 Europe A Franklinstraat 14 6003 DK Weert Netherlands P 31 0 495 580 852 F 31 0 495 580 845 Asia Pacific A Office No 918 on 9 F Shatin Galleria 18 24 Shan Mei Street Fotan Shatin Hong Kong P 852 2145 4099 F 852 2145 4477 ...

Reviews: