EGX-SF2

Installation Instructions

6

Isolated Ground Receptacle

This product incorporates an isolated ground receptacle,
identified by the orange triangle on its face. This feature may be
useful to reduce common noise in the connected equipment. Its
intended use is to reduce electrical noise (electromagnetic
interference) by purposely insulating the grounding circuit from
any metallic wiring system. The ground pin of the receptacle is
connected to the green/yellow wire and is isolated from the
metal mounting yoke of the receptacle. The accessible metal of
the product is connected to the green wire. If it is not desired to
use this feature, connect the green/yellow and green wires
together.

References

Application Guide for Isolated Ground Wiring Devices 2007.
National Electrical Manufacturers Association (NEMA)

IEEE Std 1100

-2005, “IEEE Recommended Practice for

Powering and Grounding Electronic Equipment” (Emerald
Book), Section 8.5.3.2.

IEEE Std 142™-2007, “IEEE Recommended Practice for
Grounding of Industrial and Commercial Power Systems”
(Green Book), Sections 5.5.1, 5.5.2.

NFPA-70, “National Electrical Code”, Article 250.146
Connecting Receptacle Grounding Terminal to Box.

(D) Isolated Ground Receptacles. Where installed
for the reduction of electrical noise (electromagnetic
interference) on the grounding circuit, a receptacle
in which the grounding terminal is purposefully
insulated from the receptacle mounting means shall
be permitted. The receptacle grounding terminal
shall be connected to an insulated equipment
grounding conductor run with the circuit conductors.
This equipment grounding conductor shall be
permitted to pass through one or more panel boards
without a connection to the panel board grounding
terminal bar as permitted in 408.40, Exception, so
as to terminate within the same building or structure
directly at an equipment grounding conductor
terminal of the applicable derived system or service.
Where installed in accordance with the provisions of
this section, this equipment grounding conductor
shall also be permitted to pass through boxes, wire
ways, or other enclosures without being connected
to such enclosures.

Informational Note: Use of an isolated equipment
grounding conductor does not relieve the
requirement for grounding the raceway system and
outlet box.

C22.2 No. 1, “Canadian Electrical Code, Part 1”, Rule 10-906
Bonding conductor connection to circuits and equipment.

(6) A bonding jumper shall be installed to connect
the bonding conductor to the grounding terminal of
a receptacle and in such a manner that
disconnection or removal of the receptacle will not
interfere with, or interrupt grounding continuity.

(7) In the case of metallically enclosed systems
where the grounding path is provided by the metal
enclosure, a bonding jumper shall be installed to
bond the grounding terminal of the receptacle to the
enclosure.

(8) Notwithstanding Sub-rules (6) and (7), the
bonding jumper, in the case of receptacles having
grounding terminals isolated from the mounting
strap required for special equipment, shall be

permitted to be extended directly back to the
distribution panel.

INSTALLATION

The EGX-SF2 is intended for use in installations where an
existing drywall finished wall or ceiling is present. It may only be
installed in 1/2” or 5/8” thick standard drywall using the old work
clips supplied. It may also be installed at a new work site
directly to wood or steel studs using new work clip. Proceed to

"New Work Clip" Section

 to proceed with this installation.

NOTE:

The EGX-SF2 must be connected to a 15 Amp branch
circuit.

WARNING:

IMPROPER INSTALLATION CAN RESULT IN

DEATH OR SERIOUS PERSONAL INJURY! This accessory
should be installed by qualified personnel.

EGX-SF2 Site Preparation - Drywall/Ceiling

1.

Identify a suitable wall or ceiling location for the accessory.

WARNING:

ELECTRICAL SHOCK HAZARD!

CUTTING OR DRILLING INTO ELECTRICAL WIRES
OR CABLES CAN CAUSE DEATH OR SERIOUS
PERSONAL INJURY!

 ALWAYS make certain area behind

mounting surfaces is free of electrical wires and cables
before cutting, drilling, or installing fasteners.

WARNING:

EXPLOSION AND FIRE HAZARD!

CUTTING OR DRILLING INTO GAS PLUMBING CAN
CAUSE DEATH OR SERIOUS PERSONAL INJURY!
ALWAYS make certain area behind mounting surfaces
is free of gas, water, waste, or any other plumbing
before cutting, drilling, or installing fasteners.

2.

Using a stud sensor, locate and mark studs.

NOTE:

EGX-SF2 is designed to fit in a drywall surface.

3.

Using housing as a template, draw pencil line completely
around housing.

4.

Measure the marked area and compare to the dimensions
shown in Figure 1. If measurements do not exceed the
maximum dimensions shown in Figure 1, continue to step 5.
If they do, adjust markings to match dimensions in Figure 1.

5.

Cut drywall on

outside

 edge of line and remove.

Figure 1

EGX-SF2

4-1/2” MAX

(114mm)

4” MAX

(101.6mm)

CUTOUT AREA

MINIMUM CLEARANCE

TO STUD:  3/4”

Summary of Contents for EGX-SF2

Page 1: ...truções de Instalação Istruzioni di installazione Installatie instructies Instructions d installation Power Conditioned Outlet Box Spanish Product Description German Product Description Portuguese Product Description Italian Product Description Dutch Product Description French Product Description EGX SF2 ...

Page 2: ... the installer s responsibility to make sure all components are properly assembled and installed using the instructions provided READ ALL INSTRUCTIONS BEFORE USING THIS PRODUCT DANGER TO REDUCE THE RISK OF ELECTRIC SHOCK 1 Always turn off power at source before installing the outlet WARNING TO REDUCE THE RISK OF BURNS FIRE ELECTRIC SHOCK OR INJURY TO PERSONS Always turn off power at source before ...

Page 3: ...are il fissaggio Bevestiging losdraaien Desserrez les fixations Phillips Screwdriver Destornillador Phillips Kreuzschlitzschraubendreher Chave de fendas Phillips Cacciavite a stella Kruiskopschroevendraaier Tournevis à pointe cruciforme Pencil Mark Marcar con lápiz Stiftmarkierung Marcar com lápis Segno a matita Potloodmerkteken Marquage au crayon Drill Hole Perforar Bohrloch Fazer furo Praticare ...

Page 4: ...EGX SF2 Installation Instructions 4 DIMENSIONS ...

Page 5: ...REQUIRED FOR INSTALLATION PARTS A 1 B 1 D 1 10 32 x 3 8 Earthing symbol IEC 60417 No 5019 affixed adjacent to grounding terminal Grounding screw and washer installed at factory Outlet box Outlet cover C 2 Clip E 1 New work clip F 2 12 24 x 3 8 ...

Page 6: ...t 1 Rule 10 906 Bonding conductor connection to circuits and equipment 6 A bonding jumper shall be installed to connect the bonding conductor to the grounding terminal of a receptacle and in such a manner that disconnection or removal of the receptacle will not interfere with or interrupt grounding continuity 7 In the case of metallically enclosed systems where the grounding path is provided by th...

Page 7: ...shall avoid unnecessary bends NOTE An insulated grounding conductor that is identical in size and insulation material and thickness to the grounded and ungrounded circuit supply conductors except that it is green with or without one or more yellow stripes is to be installed as part of the circuit that supplies the outlet Refer to Table 250 122 of the National Electrical Code regarding the appropri...

Page 8: ...t they are locked in place against the drywall and not laying flat against the EGX SF2 See Figure 7 Figure 7 11 Remove Phillips flat head screw and locking washer from in between outlets See Figure 7 12 Install faceplate B onto EGX SF2 using one Phillips flat head screw and locking washer removed in Step 11 See Figure 8 NOTE Make sure LED light on outlet box lines up with hole location on faceplat...

Page 9: ...n the building wiring attach it separately to the green yellow isolated ground wire on box If there is no separate green yellow isolated ground wire connect green ground wire to both green yellow isolated ground wire and green box ground wire on box NOTE The grounding conductors serving this outlet are to be connected to earth ground at the service equipment or other acceptable building earth grou...

Page 10: ...that it is locked in place against the drywall and not laying flat against the EGX SF2 See Figure 14 13 Remove Phillips flat head screw and locking washer from in between outlets See Figure 15 Figure 15 14 Install faceplate B onto EGX SF2 using one Phillips flat head screw and locking washer removed in Step 5 See Figure 16 NOTE Make sure LED light on outlet box lines up with hole location on facep...

Page 11: ...Installation Instructions EGX SF2 11 ...

Page 12: ...e com 08 17 USA International A 6436 City West Parkway Eden Prairie MN 55344 P 800 582 6480 952 225 6000 F 877 894 6918 952 894 6918 Europe A Franklinstraat 14 6003 DK Weert Netherlands P 31 0 495 580 852 F 31 0 495 580 845 Asia Pacific A Office No 918 on 9 F Shatin Galleria 18 24 Shan Mei Street Fotan Shatin Hong Kong P 852 2145 4099 F 852 2145 4477 ...