![Chicago Electric 62216 Owner'S Manual And Safety Instructions Download Page 7](http://html1.mh-extra.com/html/chicago-electric/62216/62216_owners-manual-and-safety-instructions_2598577007.webp)
Page 7
For technical questions, please call 1-888-866-5797.
Item 62216
Sa
Fety
Opera
ti
O
n
Maintenance
Setup
extension cords
1�
Grounded
tools require a three
wire extension cord�
Double Insulated
tools can
use either a two or three wire extension cord�
2� As the distance from the supply outlet increases,
you must use a heavier gauge extension cord�
Using extension cords with inadequately sized wire
causes a serious drop in voltage, resulting in loss
of power and possible tool damage�
(See table a.)
3� The smaller the gauge number of the wire, the
greater the capacity of the cord� For example,
a 14 gauge cord can carry a higher current
than a 16 gauge cord�
(See table a.)
4� When using more than one extension cord
to make up the total length, make sure
each cord contains at least the minimum
wire size required�
(See table a.)
5� If you are using one extension cord for more
than one tool, add the nameplate
amperes
and use the sum to determine the required
minimum cord size�
(See table a.)
6� If you are using an extension cord outdoors, make
sure it is marked with the suffix “W-A” (“W” in
Canada) to indicate it is acceptable for outdoor use�
7� Make sure the extension cord is properly wired
and in good electrical condition� Always replace
a damaged extension cord or have it repaired
by a qualified electrician before using it�
8� Protect the extension cords from sharp objects,
excessive heat, and damp or wet areas�
taBLe a: recOMMenDeD MiniMuM Wire
GauGe FOr eXtenSiOn cOrDS* (120/240 VOLt)
naMepLate
aMpereS
(at full load)
eXtenSiOn cOrD
LenGtH
25´ 50´ 75´ 100´ 150´
0 – 2�0
18
18
18
18
16
2�1 – 3�4
18
18
18
16
14
3�5 – 5�0
18
18
16
14
12
5�1 – 7�0
18
16
14
12
12
7�1 – 12�0
18
14
12
10
-
12�1 – 16�0
14
12
10
-
-
16�1 – 20�0
12
10
-
-
-
* Based on limiting the line voltage drop to five volts at
150% of the rated amperes.
Symbology
Double Insulated
Canadian Standards Association
Underwriters Laboratories, Inc�
V
Volts
~
Alternating Current
a
Amperes
OPM
No Load Orbits per Minute
WARNING marking concerning Risk
of Eye Injury� Wear ANSI-approved
safety goggles with side shields�
Read the manual before
set-up and/or use�
WARNING marking
concerning Risk of Fire�
Do not cover ventilation ducts�
Keep flammable objects away�
WARNING marking concerning
Risk of Electric Shock�
Properly connect power cord
to appropriate outlet�