Instructions for installation and use. Reproduction prohibited. 07/ 2010 version 2.0 TAM
21
Such reduction in cross-section must be located as close as possible
to the hood’s false ceiling. A maximum distance of 10 cm between the
false ceiling and the cross-section variation is permitted.
4.3 – Direction change
An angle of direction change is permitted as long as it does not
exceed 45°.
4.4 – Junction of connecting duct and appliance
The connecting duct may be fitted outside on the appliance’s pipe,
ascertaining complete airtightness between the duct and the pipe.
4.5 – Junction of flue and connecting duct
4.5.1 Insulated metal flue
The junction must be carried out on an insulated metal flue using the
connecting device specially designed by the manufacturer of the
insulated flue.
The whole outside section of the first part of the flue must emerge in
the room in which the fireplace is located.
The fitting between the special device and the connecting duct must
be at least 40 mm.
4.5.2 Concrete or terracotta bricked flue
The junction should be carried out using the specially designed connecting
device, in such a way as to ensure airtightness and good mechanical
performance.
The whole outside section of the first part of the flue must emerge in the
room in which the fireplace is located.
The fitting between the special device and the connecting duct must be at
least 40 mm.
4.6 – Warm air distribution
For installation of warm air distribution systems forming the subject of a
Technical Evaluation, the minimum airtightness classification is defined in
the Technical Evaluation.