SIMPLE LOGGER II
English
Page 49
MODEL
CL601
Electrical
Inputs
One
Input
Clamp-on AC ammeter
Input level
0 to 600 A
AC
Uncertainties (50 / 60 Hz)
Resolution
0 to 5 A: unspecified
5 to 50 A: ± (1% of r 1 A)
50 to 400 A: ± (1% of r 0,5 A)
400 to 600 A during < 10 min: ± (3% of r 1 A)
0,1 A
Maximum input level ***
600 A < 1 minute
Sample rate
64 samples/cycle
Storage rate
Programmable from 125ms to 1 day
Storage modes
Start/Stop, FIFO or Extended Recording Mode* (XRM™)
Recording length
Programmable using DataView
®
from 15 minutes to 8 weeks
Memory
240,000 measurements (512 kB). The recorded data is stored in non-volatile
memory retained even if the battery is low or removed.
Communication
USB 2.0 optically isolated
Power source **
2 x 1.5 V AA (LR6) cell Alkaline batteries
Battery life
100 hours to >45 days (dependent on storage rate/recording length)
Mechanical
Dimensions
136x70x32 mm (5.38x2.75x1.28")
Weight (with batteries)
485 g (1.07 lbs / 17.1 oz)
Case
Polycarbonate UL94-V0
Jaw opening
1 cable Ø 36 mm (1.42'')
2 cables Ø 25 mm (1.00'') each
2 rods 50 x 5 mm
Vibration
IEC 68-2-6 (1,5 mm 10 to 55 Hz)
Shock
IEC 68-2-27 (30 G)
Drop
IEC 68-2-32 (1 m)
Environmental
Operating temperature
- 10°C to + 50°C (14°F to 122°F)
Storage temperature
- 20°C to + 60°C (- 4°F to + 140°F)
Relative humidity
up to 85% at 35°C (95°F) without condensation
Altitude
2000 m
Safety
Conformity
EN 61010-2-032; 600 V CAT III ; Pollution level 2
Level of protection
IP 40
*See the end of chapter