6.2.1 Saving measured values (MEM)
1. Carry out the required measurement and wait for the measured value to come up on the display.
Press on the “MEM/MR” button to call the save function. “MEM” flashes and the free memory save
number following the last filled space is suggested, for example:
The display of “FREE” means that the memory space is not occupied for the chosen function
The display of “OCC ” means that the memory space is already occupied for the chosen function
If you want to change the number, press on the “SELECT” button to select the figure to be changed
and press on the “CHANGE” button to change this figure from between 0 and 9. If you choose a
memory space number already occupied by different measurements, you will be in “Saving in groups”
mode. If you choose different memory spaces each time, you will be in “Saving in series” mode.
NOTE: in “Saving in groups” mode, you can press the “CHANGE” button for 2 seconds to return to the
last save number. Pressing the “SELECT” button selects the next 10’s digit !
2. Press the “MEM” button to validate the selected number and save the values
3. Pressing “MEM” or “MORE” displays the date of the measurement. The “MORE” button is used to
display the data that has just been saved in memory.
To start a new measurement, press the “TEST” button..
To return to the display of the network voltage U
L-N
, turn the selector switch or press CHANGE or SELECT.
6.2.2 Memory recall
To make access to the memory as quick as possible, the Memory recall function (MR) is directly linked
to the exact position of the selector switch. So when a number of values are saved, simply choose the
function under which you want to recall measurements with the selector switch. When looking through
with the SELECT and CHANGE buttons (see below), the instrument suggests ONLY memory space
numbers containing measurements made under the selected function.
Example : An R
ISO
L-N-PE measurement was carried out and saved under the memory number
N°5.
Memory recall procedure:
1. Turn the selector switch to the INSULATION “R
L-N-PE
” position:
2. Press the “MR” button to activate memory recall.
3. Select n° 5 with the “CHANGE” + “SELECT” buttons.
4. Confirm by pressing “MR”: the message “OK 05” is displayed.
5. With “MORE”, bring up the saved values on the display.
6.2.3 Wiping the memory
1. Switch off the instrument with the selector switch.
2. Press the “MEM/MR” button, hold it down for 2 sec. and at the same time turn the selector switch to
switch on the instrument.
3. An indication is displayed, for example:
The display of “OCC + a figure” indicates the last space occupied by a value.
You can release the “MEM/MR” button.