Changing variable settings:
1. Turn the selector switch to the required position.
2. Press the “MORE” button several times in order to display the variables. Change them using the
“CHANGE” and “SELECT” buttons.
3. To save the changes, press the “MORE” button.
4.5 “SET UP” = General settings
This mode makes it possible to adapt the general settings on the C.A 6115N to the specific needs of the
operator, including: setting standby mode on/off, the buzzer, date, time, lead compensation, RS232
baud rate …
This makes it possible to either set up the C.A 6115N either as an extremely easy to use instrument that
displays just the main measurement results/parameters, or as a more comprehensive instrument that
besides displaying the main measurement results/parameters, also gives a number of useful secondary
results/parameters depending on the function selected.
Below is the list of general settings that are possible:
Pd
Standby mode
on/off
Set to off - prevents the standby mode from coming into effect
(saves batteries) when not used for several minutes
bu
Buzzer
on/off
Set to off - prevents monitoring of limits with audible beep
dAt Date
06 05 96
Set date using “SELECT” and “CHANGE”
tim
Time
AM 12:31
Set time using “SELECT” and “CHANGE”
R
∆
Compensation R: on/off
Set to off - removes lead compensation
bd
Baud rate: 300...9.6 K..
- - -
RS232 interface speed
When “- - -” is displayed, this signifies serial-to-parallel mode
(to be chosen for A4 parallel printer
with optional adapter. See § 7)
When “ -P-” is displayed, this means the remote control
probe can be used (see § 4.7).
prt
Print format: doc/prt
doc
: “Documentation”-type printing
prt
: “Protocol”-type printing
The rest of the SET-UP menu below lists the secondary parameters/results that can be shown or hid for
each function. The “x”’s indicate the functions where there is a parameter/result display “ON/OFF”
option:
Parameter
Setting
RCD
EARTH
LOOP INSULATION LOW
Ω
int
Interval selection
0.1...199.9 min
X
X
(auto recording mode)
U
L
Contact voltage limit
on/off
X
X
U
REF
Reference voltage for I
K
on/off
X
X
I
K
Short-circuit current
on/off
X
Z
S
Loop impedance
on/off
X
Z
S
lim
Loop impedance limit
on/off
X
X
R
S
Loop resistance
on/off
X
X
R
A
lim
Earth resistance limit
on/off
X
R lim
Resistance limit
on/off
X
X
Z
A
Earth impedance
(1)
on/off
X
X
(1) Only settable with the Utility Software Version 3.2