11
To change settings:
1. Turn the selector switch to the required position.
2. Press the “Print / SET-UP” button for over 2 seconds. – All segments of the display come on.
3. You can now press the “MORE” button several time to go through the “SET-UP” parameters and
change them accordingly using the “CHANGE” and “SELECT” buttons.
4. To quit “SET UP” and save the changes made, press the “MORE” button until you have worked all the
way through SET-UP, or press the “TEST” button. If you turn the selector switch, the changed parameter
settings will not be saved after the instrument is switched off.
4.6 Standby mode (Power down-Pd)
To prolong battery life, the instrument switches to standby mode approximately 1 minute after being left
idle – the screen indicates “ - - -”. The display can be reactivated by pressing any button.
This standby function can be deactivated in “SET UP”.
4.7 Power up information
After a short display test with all segments some numbers are indicated before the instrument switches
into the voltage measurement status. The numbers show the software version (2 digits on the left) and
the instrument number, composed of 6 digits :3 digits main display and 3 digits upper right.
Example:
28
300
001
Means:
2.8 Software version
300 001 Instrument number
4.8 Remote control probe
This probe plugs into the C.A 6115N’s RS232 socket. It is
fitted with a 4 mm safety socket on its underside, making it
possible to connect one of the three test leads, L, N, or PE.
All measurements can be carried out using the yellow button
on the probe, which is the equivalent of the “TEST” button on
the C.A 6115N.
WARNING: The test for PE-voltage (connected to earth) is
not carried out with the probe.
A push button on the back of the probe enables the operator
to light up the measurement point (approx. 500 lux.
Illumination). This function can be very handy when making
measurements on powered down installations for example.
To use the probe, first set the “bd = baud rate” to “-P”
in the
“SET-UP” menu (see § 4.5).
4.9 Error codes CA 6115N (listed according to Software Version)
V2.3:
E00 - microcontroller program check-sum error
E01 - stack overflow
E02 - program status error
E03 - display value out of range
E04 - memory (MEM/MR) check-sum error
E05 - EEPROM check-sums (one of 4)
E06 - watchdog reset
E07 - EEPROM communication
E08 - RTC initialisation or access error
E09 - bistable relays control
Remote
c o n t r o l
probe
R S 2 3 2
socket
Croc-clips