3.2 Dampness and Weatherproofing Performance
Chase EPS External Wall Cladding System complies with the NCC 2019 performance requirements for
weatherproofing and dampness.
This has been confirmed by testing in accordance with the verification method V2.2.1 in the NCC 2019.
This verification method requires that a test specimen is constructed and tested so that the weatherproofing
performance of many of the common combinations of details found in normal construction practice can be
examined.
In accordance with V2.2.1, weatherproofing compliance is demonstrated for an external wall with;
• Serviceability limit state design wind pressures of not more than +0.82kPa & -1.23kPa, this includes up to
AS 4055 N4 Wind Classification (note that 50mm thickness panel is only up to N3 applications only due
to strength); and
• Includes only windows that comply with AS 2047 (Windows and external glazed doors in buildings), and
has a Risk Score of 20 or less determined in accordance with NCC 2019, BCA Volume 2 Table V2.2.1a, as follows.
Table V2.2.1a - Risk factors and scores
(Credit: The National Construction Code Series 2019© as released by the Australian Building Codes Board on behalf of the Commonwealth of Australia and States and Territories of Australia.
http://creativecommons.org/licenses/by-nc-nd/4.0/legalcode.)
Risk factor
Category
Risk severity
Score
Wind region
Region A (AS/NZS 1170.2)
Low to medium
0
Region B (AS/NZS 1170.2)
Region C (AS/NZS 1170.2)
High
1
Region D (AS/NZS 1170.2)
Very high
2
Number of storeys
One storey
Low
0
Two storeys in part
Medium
1
Two storeys
High
2
More than two storeys
Very High
4
Roof/wall junctions
Roof-to-wall junctions fully protected
Low
0
Roof-towall junctions partially exposed
Medium
1
Roof-to-wall junctions fully exposed
High
3
Roof elements finishing within the boundaries formed by the external walls
Very High
5
Eaves width
Greater than 600mm for single storey
Low
0
451-600mm for single storey; or greater than 600mm for two storey
Medium
1
101-450mm for single storey; or 0-450mm for two storey; or less than
600mm for above two storey
High
3
0-100mm for single storey; or 0-450mm for two storey; or less than 600mm
for above two storey
Very High
6
Envelope complexity
Simple shape with single cladding type
Low
0
Complex shape with no more than two cladding types
Medium
1
Complex shape with more than two cladding types
High
3
As for high risk but with fully exposed roof-to-wall junctions
Very High
6
Decks, porches and
balconies
None; or timber slat deck or porch as ground level
Low
0
Fully covered in plan view by roof; or timber slat deck attached at first or
second floor level
Medium
2
Balcony exposed in plan view at first floor level; or balcony cantilevered at
first floor level
High
4
Balcony exposed in plan view at second floor level or above
Very High
6
Summary of Contents for CONCRETE FINISH
Page 4: ...2 1 Introduction...
Page 6: ...4 2 System Summary...
Page 9: ...7...
Page 10: ...8 3 National Construction Code NCC 2019...
Page 14: ...12 4 Materials...
Page 20: ...18 5 Specifications...
Page 22: ...20 6 Installation...
Page 29: ...27 Notes...
Page 30: ...28 7 Construction Details...