Choosing Wire Gauge
Use Table 2 and Table 3 to determine the appropriate wire gauges. Avoid unnecessarily long runs of either AC or
DC power lines.
Before working on electrical equipment, first determine there is no live power! Double check power
connections and all battery terminations.
DANGER
Avant de manipuler les équipements électriques, veillez à ce que le courant soit interrompu. Vérifiez
soigneusement les branchements à la source de courant et aux bornes de la batterie.
DANGER
Français
French
Table 2.
Minimum Wire Size to Input of C-Charger
120 VAC SHORE POWER INPUT TO C-CHARGER
Model Number
AC Amp Max
25’ Length
50’ Length
100’ Length
12405E, 12405EG
10
16 AWG
14 AWG
10 AWG
12505E, 12505EG
12
16 AWG
12 AWG
10 AWG
12605E, 12605EG
13
14 AWG
12 AWG
10 AWG
220 VAC SHORE POWER INPUT TO C-CHARGER
12405EI, 12405EIG
5
18 AWG
16 AWG
14 AWG
12505EI, 12505EIG
6
18 AWG
16 AWG
12 AWG
12605EI, 12605EIG
7
16 AWG
14 AWG
12 AWG
Table 3.
Minimum Wire Size from Output of C-Charger to Battery
C-CHARGER DC OUTPUT TO BATTERY
Model Number
DC Amp Max
15’ Length
25’ Length
12405E, 12405EG, 12405EI, 12405EIG
40
8 AWG
6 AWG
12405E, 12405EG, 12405EI, 12405EIG
40
8 AWG
6 AWG
12505E, 12505EG, 12505EI, 12505EIG
50
6 AWG
6 AWG
12505E, 12505EG, 12505EI, 12505EIG
50
6 AWG
6 AWG
12605E, 12605EG, 12605EI, 12605EIG
60
6 AWG
6 AWG
External connections to the C-Charger shall comply with the U.S. Coast Guard Electrical Regulations
(33CFR183 subpart I).
WARNING
Les branchements externes du C-Charger doivent être conformes aux réglementations de la garde
côtière américaine en matière d’électricité (no 33CFR183 section I).
MISE EN GARDE
Français
French
Making AC Connections on Terminal Block 1 (TB1)
After determining the wire lengths and gauges, make the AC wiring connections to TB1. (Refer to the Block Dia-
gram in Figure 1.) Use spade terminals, and torque the screws to 8 +/−1 inch/pounds. To make connections to
the terminal blocks: