LT93−12405E−1
Issue 1 Print 5
10
Charles Industries, Ltd. All rights reserved. Printed in the United States of America.
Step
Action
1.
Remove the small screw in the center of the unit that secures the sliding door to the top cover
2.
Gently slide the door up until it stops
3.
Bring the AC input wire in through the left side access hole on the bottom of the C-Charger
4.
Connect the WHT terminal to the white (neutral) input
5.
Connect the BLK terminal to the black (hot) AC input
6.
Connect the GRN terminal to the green (ground) input.
Do not operate this unit without the green wire connected to the C-Charger and to suitable ground at
shore connection.
DANGER
DANGER
N’utilisez pas cet appareil si le fil vert n’est pas branché au C-Charger et à une mise à la terre adéquate
au quai.
Français
French
Note:
Read this manual and all precautions before installing or making connections!
To AC
ground bus
(green)
WHT BLK GRN
+DC
+DC
+DC
−DC
TB1
TB2
30A/32V F
AST
ACTING
SLO−BLO
F2
F3
Battery 1
+
−
Battery 2
+
−
Note 1
Note 4
To AC hot (black)
To AC neutral bus (white)
Note 2
Note 3
Positive
Negative (black)
Positive (red)
Note 3
(red)
Splash Guard
PCB
DC
Fuses
(see Table 4
& Note 5
AC
Fuse
(see Table 4
& Note 5)
AC power
source
circuit
breaker
(min. size
15 amps
Battery 3
+
−
P
ositive (red)
F1
(1240 EL shown)
12A/250V
Notes
1. AC stranded wire (see Table 2).
2. DC stranded wire (see Table 3).
3. External fuse/circuit breaker installed within 72” of C-Charger. (See Coast Guard Reg. 33CFR183 subpart I.)
4. Black jumper (common negative) - minimum 8 AWG (only necessary if batteries are not pre-wired with common negative).
5. Internal fuse size is for 40-amp model. See Table 4 for 50- and 60-amp model fuse sizes.
Access to
PCB TB1 &
TB2 termi-
nals & F1, F2
& F3 fuses
Figure 1. 40-, 50- and 60-Amp 5000 Series Block Diagram