2

110503-1

Installation

NOTE:

  The pump comes installed.  The belt, motor pulley, and motor cord 

and fl oat are included in the cabinet, the motor is shipped separately.

CAUTION:

  

Make sure that the mounting surface is strong 

enough to support the operating weight of the cooler when in use.  
(For operating weight, see Specifi cation Table.)

CAUTION:

  

Never plug in cooler until installation is complete 

and unit has been tested for rigidity.

• Install Duct Adapters.

  If desired, a 4 piece duct 

adapter is available as an optional accessory.  
Call 1-800-643-8341 to obtain these from the 
factory.  Align the holes in the duct adapter to the 
holes in the blower opening and attach using the 
provided screws (see Fig. 1).  Repeat for all four 
sides.  Note:  All 4 pieces are identical except for 
models 5000SD & N55/65S which have an offset 
piece which attaches to the bottom of the outlet.  
To install this offset piece, remove the screws 
holding the cut-off plate and slide the offset duct 
adapter between the blower opening and the cut-
off plate.  You may need to loosen other screws 
to do this.  Line up the holes and secure with the 
screws previously removed.

Motor Installation

• 

Install motor cord.

  For typical 120V op-

eration, connect motor cord to motor using 
the following color code: Black - Hi, Red 
- Low, White - Com., Green - Ground. (See 
Wiring Diagrams)

• 

Mount motor.  

Install blower motor in the 

motor mount yokes, adjusting the yoke 
if necessary.  Fasten with the provided 
mounting clips (see Fig. 2).

• 

Install pulley.

  Install the adjustable mo-

tor pulley so that it aligns with the blower 
drive pulley (see Fig. 3) and tighten set 
screw.

Electrical Installation

WARNING:

  

Disconnect all electrical service that will be used 

for this unit before you begin the installation.

Com.

To Switch

Pump

Motor

Blower Motor

Red
Orange
Green

Black

Ground

Com.

Lo

Hi

= Wire Nut

Ground

Lo

Hi

Pump

Black

Red

White

Orange

Green

Green

Orange

Brown

White

Blue/Black

Motor 
Clips

Adjustable 
Yoke

Fig. 2

• 

Remove junction box.

  The elec-

trical junction box is located in the 
upper inside corner of the cooler 
cabinet.  Remove the two screws 
and remove the junction box (Fig. 
4).  Slide receptacles into slots in 
junction box.

• 

Hook up electrical.

  Electrical hook up should be done by a qualifi ed 

electrician, so that all electrical wiring will conform to your local standards.  
This unit is suppled with a 120V pump.  For 240V pump operation, a 240V 
pump must be purchased.  The fan and pump receptacles will support both 
120V and 240V installations.  See the wiring diagrams for 120V and 240V 
installations.  

Note: 

 Clip pump cord onto cord clip located on the bottom 

of the junction box to keep cord our of the water.

 IMPORTANT:

  When a single speed motor is used, do not use the red 

lead on the receptacle and motor plug wiring.  Tape off end of both of the 
red leads.

CAUTION:

 

 Pump receptacle is for grounded evaporative 

cooler pump only.  Do not plug anything else into receptacle.

WARNING:

  

Make sure the cooler cabinet is properly ground-

ed to a suitable ground connection for maximum safety.

Water Connection

• 

Install overfl ow assembly.

  Place drain nipple 

through the hole in the pan, with the rubber 
washer between the pan and the head of the 
drain nipple (Fig. 6).  Screw on  nut and draw 
up tight against bottom of pan.  Insert the 
overfl ow pipe in the nipple to retain water.  
The overfl ow pipe may be removed to drain 
the pan when necessary.  A garden hose may 
be screwed on the drain nipple to drain water 
away from your unit.

• 

Connect water supply line.

  Find the 

closest supply of water.  Use a saddle 
valve (Fig. 7) to connect 1/4” tubing to 
the cold water supply or use a Sillcock 
and water valve connected to an out-
side faucet (Fig. 8).  Place the nut and 
ferrule on the tubing and tighten the 
nut until water tight.  

IMPORTANT:

  

Do not connect the water supply to any 
soft water applications.  Soft water 
will cause corrosion and decrease the 
life of the cooler.

Wiring Diagrams

240 Volts

Fig. 5

120 Volts

Champion Air Balancing Method

1.  Take a piece of tissue paper and cut it lengthwise into 3 equal strips.
2.  Turn your cooler on high cool.
3.  Open one window at least six inches wide in each room that you want 

to cool.

4.  Take the piece of tissue paper and put it up against the screen of the open 

window furthest from the cooler discharge opening.  Let go of it.  It will 
do one of three things.

IF

 

It falls down.

THEN

 

CLOSE all of the windows one inch and try step 4 again.

IF

 

It plasters itself to the screen.

THEN

 

OPEN all of the windows one inch and try step 4 again.

IF

 

It stays on the screen lightly.

THEN

 

PERFECT.  You are done.  Enjoy your cooler.

NOTES:

•  When switching to low cool, you must rebalance your home.  Repeat step 

4.

•  Once you balance your home you can cool some areas more than others by 

opening those windows more and closing the others by the same amount.  
Repeat step 4 to make sure your home is still air balanced.

Blue/Black

White

Brown

Orange

Green

Green

Orange

White

Red

Black

Pump

Hi
Lo
Com.

Ground

= Wire Nut

Hi
Lo
Com.
Ground

Black

Green

White

Red

Blower Motor

Pump

Motor

To Switch

Blower 

Housing

Motor 
Pulley

Blower 
Pulley

Fig. 3

Rubber Washer

Overfl ow Pipe

Nipple

Bottom Pan

Nut

Fig. 6

Cold
Water
Pipe

Saddle 
Valve

1/4” Tubing

Fig. 7

Fig. 1

Duct Adapter

Cut-Off Plate

Screws

Fig. 4

Junction Box

Clip

Summary of Contents for ESSICK 3000 DD

Page 1: ... filter pads where the air is cooled by evaporation and then circulated throughout the building It is this combination of cooled air and the movement of air over the skin which makes it feel cool www championcooler com CHAMPION ESSICK Evaporative Cooler Manual Unlike refrigeration systems which recirculate the air an evaporative cooler continually brings in fresh air while exhausting old air You a...

Page 2: ...0V installations Note Clip pump cord onto cord clip located on the bottom of the junction box to keep cord our of the water IMPORTANT When a single speed motor is used do not use the red lead on the receptacle and motor plug wiring Tape off end of both of the red leads CAUTION Pump receptacle is for grounded evaporative cooler pump only Do not plug anything else into receptacle WARNING Make sure t...

Page 3: ...When cooler is not used for extended periods unplug the motor and pump from inside cooler Cover unit To protect the life of the finish a cover for the unit is suggested in extended periods of non use By following the operating installation and maintenance suggestions as outlined you can get many years of efficient and satisfactory service from your cooler In the event additional information is des...

Page 4: ...lown Circuit breaker tripped Electric cord unplugged or damaged 2 Belt too loose or tight 3 Motor overheated Belt too tight Blower bearings dry Motor pulley diameter too large 4 Motor locked 1 Insufficient air exhaust 2 Belt too loose 3 Pads plugged 4 Motor underloaded 1 Inadequate exhaust in house 2 Pads not wet Pads plugged Open spots in pads Trough holes clogged Pump not working prop erly 1 Che...

Page 5: ...ner Sujetador De La Bomba 110714 110714 110714 26 Air Baffle Bafle De Aire 224112 001 224108 003 27 Float Bracket Soporte Del Flotador 216001 003 216001 003 216001 003 28 Tube Water Delivery Tubo De Agua 310716 310716 310716 30 Over Flow Assembly Montaje De Desagüe 3OA 1 3OA 1 3OA 1 31 Water Distributor Assembly Sistema Del Distribuidor De Agua 3D 4 3D 5 3D 6 32 Holder Water Distributor Soporte Pa...

Page 6: ...31D 1 3 125 175 33 7 16 28 1 8 28 1 8 13 5 8 13 5 8 4001DD N43 48D 1 3 1 2 165 166 232 233 34 1 2 34 1 8 34 1 8 17 3 4 17 3 4 5000DD N56 66D 1 2 3 4 222 226 305 309 42 7 16 39 39 19 3 4 19 3 4 3000SD N30S 1 3 116 193 33 7 16 28 1 8 28 1 8 13 5 8 13 5 8 4001SD N40 45S 1 3 1 2 154 155 268 269 34 1 2 34 1 8 34 1 8 17 3 4 17 3 4 5000SD N55 65S 1 2 3 4 204 208 353 357 42 7 16 39 39 19 3 4 19 3 4 Includ...

Page 7: ...215 4L 560 1 2 110446 110447 1 2 115 9 8 5000DD N56 66D 5000SD N55 65S 1 2 110446 110447 1 2 115 9 8 110278 DD D 110214 4L 690 SD S 110213 4L 670 3 4 110448 110449 1 2 115 13 8 Parts Drawing Dibujo De Piezas 3000SD 4001SD 5000SD N30S N40 45S N55 65S 1 2 Bore x Adjustable O D Taladro de 1 2 pulgadas x Diámetro Externo Ajustable Amperage shown is from National Electric Code Use motor nameplate for m...

Page 8: ...lla Para La Bomba 281001 001 281001 001 281001 001 25 Pump Assembly Bomba 110436 110436 110436 26 Pump Retainer Sujetador De La Bomba 110714 110714 110714 28 Tube Water Delivery Tubo De Agua 310716 310716 310716 29 Duct Adapters Adaptores Del Conducto 324016 001 324016 002 324016 003 30 Over Flow Assembly Montaje De Desagüe 3OA 1 3OA 1 3OA 1 31 Water Distributor Assembly Sistema Del Distribuidor D...

Page 9: ...ior del aparato antes de instalar o realizar cualquier labor de mantenimiento 4 Su enfriador funciona con corriente alterna de 120V o 240V de una fase y 60 Hz ciclos 5 El motor y la bomba están provistos de clavijas moldeadas con toma de tierra y se apagarán automáticamente en caso de sobrecalenta miento Los motores volverán a funcionar cuando se enfrían ADVERTENCIA Para reducir el riesgo de incen...

Page 10: ...el motor Instale la polea ajustable del motor para que queda alineada con la polea del ventilador véase fig 3 y apriete el tornillo Instalación Eléctrica ADVERTENCIA Desconecte todos los servicios eléctricos que serán usados en esta unidad antes de instalar el enfriador Quite la caja de empalme La caja de empalme se encuentra en el rincón superior del inte rior del enfriador Quite los dos tornillo...

Page 11: ... de instalar el enfriador completo ajuste la polea al diámetro mínimo y ajuste la tensión de la correa Vea la sección de mantenimiento para ajustar la tensión de la correa Poner en marcha la unidad Instale todas las rejas con los filtros prenda la bomba y permita que siga funcionando hasta que todos los filtros estén mojados Revise el amperio Con los filtros mojados y la unidad en funciona miento ...

Page 12: ... la rueda están secos Diámetro de la polea del motor demasiado grande 4 Motor parado 1 Insuficiente abertura para que salga el aire 2 Poca tensión en la banda 3 Filtros obstruidos 4 Agua insuficiente en los filtros 1 El agotamiento del aire es inadecuado 2 Los filtros no están mojados Filtros obstruidos Filtros agujereados Agujeros de los canales obstruidos Bomba no funciona 1 Revise la corriente ...

Reviews: