Operation

For the best cooling performance, if the pads are dry, pre-wet the pads 
by running the pump for a few minutes before starting the blower.

These coolers may also be used without water for ventilation purposes.  
When outside air is cool (for example, at night) or when humidity is 
high the water pump can be turned off.

IMPORTANT:

  To cool effi ciently, you must exhaust the stale or used 

air from the building.  Open windows or doors or use exhaust fans 
located away from the cooler and in the direction you wish to cool 
the air.  The air will fl ow in the direction of the exhaust openings.  A 
common guide for the amount of exhaust opening needed is to have 
at least 2 square feet of opening per 1000 CFM.

Safety Rules

1. Read instructions carefully.

2. Disconnect all electrical service that will be used for the unit before 

you begin the installation.

3. Electrical hook up should be done by a qualifi ed electrician, so 

that all electrical wiring will conform to your local standards.

4. For a maximum safety precaution, make sure cooler cabinet is 

properly grounded to a suitable ground connection.

5. Cooler must be connected to proper line current, voltage and cycle, 

as stamped on cooler motor and pump motor specifi cation plate.

6. Do no allow pump to tip over and become submerged.

7. Always 

DISCONNECT POWER

 before installing unit or 

performing any maintenance.

Installation

CAUTION:

  Make sure that the mounting surface is strong 

enough to support the operating weight of the cooler when in use.  
(For operating weight, see Specifi cation Table.)

CAUTION:

  Never plug in cooler until installation is complete 

and unit has been tested for rigidity.

CAUTION:

  Make sure all bolts are securely tightened before 

starting the cooler.

• Ductwork.

  See the General Specifi cation table for the duct open-

ing dimension for your specifi c cooler.  For down discharge units 
models 10/12DD and 14/21DD, the duct must go inside the opening.  
Size these ducts slightly smaller than the duct opening in the cooler.  
On 75/85DD  and 95DD models the duct may go to the inside or 
outside of the duct fl ange.  The side discharge units have a 1 inch 
fl ange.  Size these ducts larger than the duct opening to fi t over the 
fl ange of these units.

Note:  Curbs are not provided.  The installer is responsible for 
providing curbs or other means to support the cooler.

Water Connection

• 

Overfl ow assembly.

  Remove nut and place nipple through the hole 

in the pan, with the rubber washer between the pan and the head 
of the drain nipple (Fig. 3).  Screw on  
nut and draw up tight against bottom 
of pan.  Insert overfl ow pipe in nipple 
to retain water.  Overfl ow pipe may be 
removed to drain pan when necessary.  
A garden hose may be screwed on the 
drain nipple to drain water away from 
your unit.

• Pump.

  The pump must be secured to prevent it from tipping over.  

Secure the pump to the pump mounting bracket.  For the 10/12 and 
14/21 models, remove the mounting screw on the top of the pump 
and using this same screw, secure the pump to the pump mount.  To 
secure the pump for the 75/85 and 95 models, slide the pump into 
the slot of the pump mount and secure with the plastic retainer.

Motor Installation

• 

Mount motor.

  Slide the heads of the provided carriage bolts into 

the slots of the adjustable channels.  Slide these channels sideways 
in the slotted holes to align with the holes in the motor base and to 
align the motor shaft with the blower pulley.  Mount the motor to 
the motor mount using these carriage bolts and the washers and nuts 
provided (see Fig. 1).  Make sure all bolts are securely tightened.

• 

Install pulley.

  Install the adjustable motor pulley so that it aligns 

with the blower drive pulley (see Fig. 2) and tighten set screw.  See 
page 3 for instructions on adjusting pulley.

Electrical Installation

NOTE:

  Local building code regulations must be observed.

WARNING:

  Disconnect all electrical service that will be used 

for this unit before you begin the installation.

• 

Electrical Supply.

  Cooler must be supplied with the proper line 

current, voltage and frequency, as stamped on cooler motor and 
pump motor specifi cation plate.  See the wiring diagrams on page 
4 for typical electrical connections.  

NOTE:

  Connecting improper 

voltage to motor will void motor warranty.

• 

Wire sizing.

  The conductor sizes are to be determined by motor 

loads and length of run per national and local electrical codes.  

• 

Switches or contactors.

  Motors require switches or contactors 

of proper current capacity and should be sized and installed by a 
competent electrician.

WARNING:

  Make sure that cooler cabinet is properly 

grounded to a suitable ground connection for maximum safety.

Fig. 1

Adjustable 
Channels

Blower 

Housing

Motor 
Pulley

Blower 
Pulley

Fig. 2

Rubber Washer

Overfl ow Pipe

Nipple

Bottom Pan

Nut

Fig. 3

Summary of Contents for 10/12 DD

Page 1: ...bleshooting 5 Warranty 5 Parts Drawing Dibujo de Piezas 10 12SD 14 21SD 6 Parts Drawing Dibujo de Piezas 10 12DD 14 21DD 7 Table Of Contents Parts List Lista de Piezas 10 12 14 21 8 Parts List Lista de Piezas 75 85 95 9 Parts Drawing Dibujo de Piezas 75 85DD 95DD 10 Parts Drawing Dibujo de Piezas 75 85SD 95SD 11 Motor Specifications Especificaciones del Motor 75 85DD 95DD 10 Motor Specifications E...

Page 2: ...sible for providing curbs or other means to support the cooler Water Connection Overflow assembly Remove nut and place nipple through the hole in the pan with the rubber washer between the pan and the head of the drain nipple Fig 3 Screw on nut and draw up tight against bottom of pan Insert overflow pipe in nipple to retain water Overflow pipe may be removed to drain pan when necessary A garden ho...

Page 3: ...is for your safety Spring Start Up Belt tension Check belt tension and readjust if needed Oil bearings The blower bearings and cooler motor in this unit should be oiled with a few drops of non detergent 20 30 weight oil once each year The motor does not need oil if it has no oil lines for oiling Motors that have no oil lines are lifetime oiled at the factory and require no further oiling for the l...

Page 4: ...tch Motor Full Load Current See Note 1 Fuses See Note 1 Main Disconnect See Note 1 Disconnect Switch At Cooler See Notes 1 2 Disconnect Switch At Cooler See Notes 1 2 Pump Motor Blower Motor Equipment Ground T1 T2 T3 Cooler Cabinet See Note 3 L2 Transformer See Note 1 208 240 or 480V 3 Phase Power Supply H P Three phase single speed blower motor Three pole motor starter with overload protection 12...

Page 5: ...e parts 1 Open windows or doors to increase air flow 2 Check water distribution system Clean pads Repack pads Clean Replace or clean pump Unplug 1 Open doors or windows Motor cycles on and off Noisy Inadequate cooling Excessive humidity in house Register your product online at www championcooler com eac onlineregistration eac htm Limited Warranty This warranty is extended to the original purchaser...

Page 6: ...6 110525 Replacement Parts Piezas De Repuesto 10 12 SD 14 21 SD ...

Page 7: ...7 110525 Replacement Parts Piezas De Repuesto 10 12 DD 14 21 DD ...

Page 8: ...12 002 214112 002 214112 003 214112 003 21 Bearing Mount Support Soporte Para Los Cojinetes 214116 001 214116 005 212103 001 212102 001 22 Blower Housing Caja De La Rueda 320116 001 320116 001 320117 001 320117 001 23 Pulley Blower Wheel Polea De La Rueda 110281 110281 110298 110298 24 Cut Off Plate Placa Externa 318112 004 318112 004 318112 003 318112 003 25 Air Baffle Bafle Del Aire 220116 002 2...

Page 9: ...2 220116 006 27 Bearing Mount Support Soporte Para Los Cojinetes 214118 001 214115 006 28 Motor Mount Crossbrace Travesaño De La Montura Del Motor 214001 005 214001 005 29 Motor Mount Support Right Soporte Para El Montura Del Motor Direcho 214118 004 214115 002 30 Motor Mount Support Left Soporte Para El Montura Del Motor Izquierdo 214118 004 214115 002 31 Channel Retainer Support Retendedor De Ca...

Page 10: ... 1 0 6 1 0 Static 110302 0 0 8 Static 110299 0 6 1 0 Static 95 DD 1 1 2 110459 1 110463 9 1 3 1 1 115 208 230 208 230 460 5 8 7 8 110217 4L 830 110279 003 0 0 7 Static 110306 1 0 4 1 0 Static 110302 0 0 7 Static 110299 0 4 1 0 Static 2 110460 1 110464 9 1 3 1 1 115 208 230 208 230 460 7 8 7 8 110217 4L 830 110299 0 1 0 Static 3 110465 9 3 1 208 230 460 1 1 8 110218 4L 850 110304 0 0 6 Static 11030...

Page 11: ...10458 110462 9 1 1 3 1 2 1 115 208 230 230 230 460 5 8 5 8 7 8 110217 4L 830 110279 003 Static 0 8 110306 1 Static 0 6 110302 Static 0 8 110299 Static 0 6 95 SD 1 1 2 110459 1 110463 9 1 3 1 1 115 208 230 230 460 5 8 7 8 110217 4L 830 110279 003 Static 0 6 110306 1 Static 0 2 110302 Static 0 6 110299 Static 0 2 2 110460 1 110464 9 1 3 1 1 115 208 230 230 460 7 8 7 8 110217 4L 830 110299 Resilient ...

Page 12: ...3 1 1 115 208 230 208 230 460 7 8 7 8 110219 B 108 110290 Static 0 6 110289 Static 0 4 3 110465 9 3 1 208 230 460 1 1 8 110219 B 108 110291 5 110466 9 3 1 208 230 460 1 1 8 110219 B 108 110291 Static 0 6 110304 1 Static 0 4 14 21 SD 1 1 2 110459 1 110463 9 1 3 1 1 115 208 230 208 230 460 5 8 7 8 110219 B 108 110290 110286 2 110460 1 110464 9 1 3 1 1 115 208 230 208 230 460 7 8 7 8 110219 B 108 110...

Page 13: ... pernos provistos con cuellos cuadrados por la ranura en la montura ajustable del motor Conectar El Agua La instalación del montaje de desagüe Quite la tuerca y pase la boquilla por el agujero de la bandeja colocando la arandela de hule entre la bandeja y la cabeza de la boquilla véase fig 3 Coloque la tuerca en la boquilla y atorníllela hasta que quede apretada contra la parte inferior de la band...

Page 14: ...r lubricados usando unas gotas de un aceite no detergente de densidad 20 30 una vez al año No obstante los motores sin tuberías para aceite no necesita ser lubricados Estos motores son lubricados en la fábrica de por vida y no requieren nunca ninguna lubricación PRECAUCIÓN No lubrique demás El agregar demasiado aceite puede ocasionar que se queme el motor a causa del aceite entrando al interior de...

Page 15: ...ador Vea Las Notas 1 2 Desconectador Al Enfriador Vea Las Notas 1 2 Motor De La Bomba Motor Del Ventilador Tierra De Equipo T1 T2 T3 Caja Del Enfriador Vea Nota 3 L2 Transformador Vea Nota 1 Alimentación Eléctrica 208 240 o 480V Trifásica H P Motor trifásico del ventilador de una velocidad Arrancador de tres polos con protección de sobrecarga Motor de la bomba de 120V y una fase con alimentación e...

Page 16: ...ba no trabaja ade cuada Insuficiente flujo de agua Problema Causa Posible Remedio Problema Causa Posible Remedio La Localización De Averias No arranca o no sale aire Sale poco aire cuando la unidad está funcionando Enfriamiento inadecuado Motor se apaga y se enciende Hace Ruido Demasiada humedad en la casa Olor a ence rrado olor desagradable Garantía Limitada La presente garantía se extiende al co...

Reviews: