48
Solar usage guide
All performance metrics are estimates and are subject to change at any time. Actual results will vary due to variables specific to the site.
Typical System Standby Battery Current Consumption (mA)
System voltage
24V
Main board with no radios programmed
2.7 mA
One or more LiftMaster
®
remote controls programmed
+1 mA
myQ
®
device or wireless dual gate programmed
+2.4 mA
Expansion board
+11.1 mA
Relay adapter board
+11.1 mA
Per loop detector LOOPDETLM (up to 3 loop detectors can be plugged in to the expansion board)
+3.8 mA
Add up current draw by feature and accessory to determine total current draw
NOTE:
The use of photoelectric sensor heaters (models LMRRUL and LMTBUL) is NOT recommended in solar applications.
SOLAR GATE CYCLES PER DAY - 22 ft. 2,500 lb. gate
BATTERY CURRENT
DRAW (mA)
ZONE 1
ZONE 2
ZONE 3
7AH batteries 33AH batteries 7AH batteries 33AH batteries 7AH batteries 33AH batteries
20W SOLAR PANEL
5
14
16
15
12
15
20
12
14
50
11
100
40W SOLAR PANEL
5
25
36
15
22
15
24
35
14
20
20
24
34
34
20
100
14
23
10
200
11
60W SOLAR PANEL
5
32
57
19
34
14
15
30
55
18
33
13
20
30
54
17
32
13
100
19
43
22
250
22
SOLAR PANELS