Plug In Transformer Power
Wire plug in transformer power as shown.
Plug in transformer
Control Board
Set switch to
WALL XFMR
AC Power Switch
The AC switch on the operator turns the incoming 120/240 Vac power ON or OFF. The AC switch ONLY turns off AC power to the control board and DOES
NOT turn off battery power.
Battery Switch
The battery switch turns the battery power on or off.
AC Power Switch
Battery Switch
Step 9 Connect Batteries
7AH Batteries
The batteries are charged in the circuit by the integrated transformer.
1. Turn the AC power switch to OFF.
2. Turn the battery switch OFF .
3. Connect a jumper between the po) terminal of the battery to
the negative terminal(-) of the other battery.
4. Connect the red battery wire from the operator to the po)
terminal of the battery.
5. Connect the black battery wire from the operator to the negative (-)
terminal of the battery.
6. Turn the battery switch ON .
7. Turn the AC power switch to ON to restore AC power.
Battery Wiring
Red Wires
Black Wires
Jumper
INSTALLATION