Installation, Operation & Maintenance                                                                                   Merlin CO2 TFT

 

 

 

Rev 1   05-21 

8  

Operation 

   Initial Power-Up & Indicators 

 
On connecting power, the CO2-TFT monitor enters a stabilisation phase for approximately 60 seconds – during this 

period, your device not yet ready for operation. 

 
 

 

a.

 

CARBON DIOXIDE READING 
Current CO

2

 gas level in parts per million (ppm). 

 

b.

 

0-10V ANALOGUE OUTPUT LEVEL  
0-10V analogue outputs one and two. 

 

c.

 

FLAME ICON  
Appears only when the CO2-TFT receives a signal 
from a gas valve and gas supply is open/on and set 
to Natural or Mechanical Ventilation Type mode.  

 

d.

 

BOOST ON  
Message appears when BOOST is activated - press and hold the touch button (f) for three (3) seconds. The 
analogue outputs will run at optimum voltage (10V) for a pre-set number of minutes. Boost can only be activated 
if either analogue outputs is set to CO2

 

or DUAL mode only.  

 

e.

 

MUTE  
Message appears when the touch button (f) is pressed. The audible alarm buzzer must be set to on or every 10 
minutes and can only occur when gas is in use or KITCH. Ventilation mode is selected and when CO

2

 levels rise 

above 2800ppm. 

 

f.

 

VENTILATION MODE 
Displayed under normal operation. K (Kitchen) / M (Mechanical) / N (Natural). The mode determines the 
configuration and alarm levels. 

 

g.

 

TOUCH BUTTON  
To activate Boost or Mute feature and to view the screen for 10 seconds during screen saver mode. 

 

h.

 

TEMPERATURE READING  

 

i.

 

GAS IN USE MESSAGE  
Appears only when the CO2-TFT receives a signal from a gas valve and gas supply is open/on.  
When the gas valve is closed, this message is not displayed.  
Appears with Flame Icon. 

 

j.

 

BLANK – see K. 
(Natural or Mechanical mode), this is left blank when the current CO

2

 reading is below 550ppm.  

In kitchen ventilation mode – this is constantly left blank. 

 

k.

 

AVERAGE CO

2

  

The monitor will display the average CO

2

 reading over periods of 8 hours and appear only when current CO

2

 

levels reach or exceed 600ppm.  
Natural or Mechanical ventilation type modes only. 

 
 

 

 

Summary of Contents for Merlin CO2 TFT

Page 1: ...omatically switch between ventilation programs when gas is used Boost Mute and Wake Up feature Installation Operation Maintenance Please read this manual carefully and retain for future use The Merlin...

Page 2: ...unting 4 Board Overview 4 Wiring your CO2 TFT 5 Configuration Settings 6 Configuration 6 Factory Set Condition 7 Operation 8 Initial Power Up Indicators 8 Traffic Light Indicator 9 Alarms Configuratio...

Page 3: ...ed to replacement of the product with repaired product at the discretion of the manufacturer This warranty is void if the product has been damaged by accident unreasonable use neglect tampering or oth...

Page 4: ...here possible monitors must be fixed in such a position as to allow natural air circulation These recommended heights may vary based on airflow and temperature conditions in addition to the proposed a...

Page 5: ...n mode until the gas supply is turned off see Settings for configuration Recommended for teaching areas with gas appliances such as laboratories and food technology rooms CO2 ALARM Not a mains output...

Page 6: ...hts setting red Press to save desired setting Configuration NAT Natural Ventilation Mode Recommended for buildings without mechanical ventilation Pre Alarm 1300ppm 23 C 73 4 F Alarm 1500ppm 25 C 77 0...

Page 7: ...minutes Boost can be activated only if analogue outputs are set to either CO2 or DUAL mode only Select 1 2 3 4 5 6 7 8 9 10 minute s FAN ENABLE Fan switch is energised by CO2 ON 600ppm OFF 550ppm TEM...

Page 8: ...ears when the touch button f is pressed The audible alarm buzzer must be set to on or every 10 minutes and can only occur when gas is in use or KITCH Ventilation mode is selected and when CO2 levels r...

Page 9: ...Default Green 1500ppm 23 C 73 4 F Yellow 1500ppm 23 C 73 4 F Red 2800ppm 25 C 77 0 F CO2 Pre alarm relay switch 2800ppm CO2 Alarm relay switch 4500ppm 0 10V Analogue Output Progression Min output 1 5...

Page 10: ...e device High concentrations of alcohol found in many products may damage deteriorate or affect the gas sensing elements such as wine deodorants stain removers thinners etc Auto Calibration Our CO2 se...

Page 11: ...30mm 5 51 x 3 74 x 1 18 Unit Weight Approx 0 08kg Housing Material Polylac PA765 Environmental Ingress Protection IP40 Storage Conditions Dry Temp 10 50 C 14 122 F 30 80 rh Compliance CE EN 50270 EN 6...

Page 12: ...or any errors or omissions in this document or their consequences CGS would greatly appreciate being informed of any errors or omissions that may be found in the content of this document For informati...

Reviews: