Installation, Operation & Maintenance                                                                                   Merlin CO2 TFT

 

 

 

Rev 1   05-21 

6  

 

0-10V ANALOGUE OUTPUT 1 & OUTPUT 2 
These connections are used to regulate external fan speed controllers (supplied 
separately). Connect direct to fan speed controllers or via your Merlin panel [0-
10V] terminal if available. Minimum voltage output can be configured in settings 
menu from zero to 5 volts. 
 
0-10V output can be driven by the status of current CO

level only, by current 

temperature only or by the status of both levels (whichever is greatest). 
 

 

 
12-24V (AC or DC) POWER 
To power the CO2 TFT with 12-24v power – this should be supplied to the [12-24V 
POWER INPUT] connector (+ / -). 
 
This connection can be either AC or DC. 
 
 

 
 

   Configuration Settings  

 

There is a settings switch on the CO2-TFT board. Switch it on to prompt the on-screen menu. Navigate the menu 

using the buttons on the board. When changes have been made – turn the settings switch off. 
 

[SEL.] button 

 

Scroll through functions (highlighted red). 

 

Change the desired setting when highlighted. 

[OK] button 

 

Highlights setting (red). 

 

Press to save desired setting.  

 
 

   Configuration 

 

NAT. - 

Natural Ventilation Mode 

(

Recommended for buildings without mechanical ventilation). 

 

Pre Alarm:  >1300ppm   >23 °C/ 73.4°F    
Alarm:         >1500ppm   >25 °C/ 77.0°F 
CO

Pre-alarm relay switch: 1300ppm 

CO

Alarm relay switch:        1500ppm 

0-10V Analogue Output: Linear Progression. 
Min output (1-5V) from 600ppm   23 °C/ 73.4°F 
Max  output (10V) from 1500ppm   27 °C/ 80.6°F 
Boost from: 400

 

- 1499ppm   0°C/32°F – 26.9°C/ 80.4°F 

 

MECH. - 

Mechanical Ventilation Mode (Recommended for buildings with mechanical ventilation). 

 

Pre Alarm:  >800ppm   >23 °C/ 73.4°F    
Alarm:         >1000ppm   >25 °C/ 77.0°F 
CO

Pre-alarm relay switch: 800ppm 

CO

Alarm relay switch:       1000ppm 

0-10V Analogue Output: Linear Progression. 

Min output (1-5V) from 600ppm   23 °C/ 73.4°F 
Max  output (10V) from 1000ppm   27 °C/ 80.6°F 

Boost from: 400 - 999ppm   0°C/32°F – 26.9°C/ 80.4°F 
 

KITCH. – 

Kitchen/Gas in Use Ventilation Mode (Recommended for kitchen environments).

 

 

Pre Alarm:  >1500ppm   >23 °C/ 73.4°F    
Alarm:         >2800ppm   >25 °C/ 77.0°F 
CO

Pre-alarm relay switch: 2800ppm 

CO

Alarm relay switch:       4500ppm 

0-10V Analogue Output: Linear Progression. 

Min output (1-5V) from 600ppm    23 °C/ 73.4°F 
Max  output (10V) from 2800ppm   27 °C/ 80.6°F 

Boost from: 400 - 2799ppm   0°C/32°F – 26.9°C/ 80.4°F 
Buzzer / Mute 
from: >2800ppm  

 

 

Summary of Contents for Merlin CO2 TFT

Page 1: ...omatically switch between ventilation programs when gas is used Boost Mute and Wake Up feature Installation Operation Maintenance Please read this manual carefully and retain for future use The Merlin...

Page 2: ...unting 4 Board Overview 4 Wiring your CO2 TFT 5 Configuration Settings 6 Configuration 6 Factory Set Condition 7 Operation 8 Initial Power Up Indicators 8 Traffic Light Indicator 9 Alarms Configuratio...

Page 3: ...ed to replacement of the product with repaired product at the discretion of the manufacturer This warranty is void if the product has been damaged by accident unreasonable use neglect tampering or oth...

Page 4: ...here possible monitors must be fixed in such a position as to allow natural air circulation These recommended heights may vary based on airflow and temperature conditions in addition to the proposed a...

Page 5: ...n mode until the gas supply is turned off see Settings for configuration Recommended for teaching areas with gas appliances such as laboratories and food technology rooms CO2 ALARM Not a mains output...

Page 6: ...hts setting red Press to save desired setting Configuration NAT Natural Ventilation Mode Recommended for buildings without mechanical ventilation Pre Alarm 1300ppm 23 C 73 4 F Alarm 1500ppm 25 C 77 0...

Page 7: ...minutes Boost can be activated only if analogue outputs are set to either CO2 or DUAL mode only Select 1 2 3 4 5 6 7 8 9 10 minute s FAN ENABLE Fan switch is energised by CO2 ON 600ppm OFF 550ppm TEM...

Page 8: ...ears when the touch button f is pressed The audible alarm buzzer must be set to on or every 10 minutes and can only occur when gas is in use or KITCH Ventilation mode is selected and when CO2 levels r...

Page 9: ...Default Green 1500ppm 23 C 73 4 F Yellow 1500ppm 23 C 73 4 F Red 2800ppm 25 C 77 0 F CO2 Pre alarm relay switch 2800ppm CO2 Alarm relay switch 4500ppm 0 10V Analogue Output Progression Min output 1 5...

Page 10: ...e device High concentrations of alcohol found in many products may damage deteriorate or affect the gas sensing elements such as wine deodorants stain removers thinners etc Auto Calibration Our CO2 se...

Page 11: ...30mm 5 51 x 3 74 x 1 18 Unit Weight Approx 0 08kg Housing Material Polylac PA765 Environmental Ingress Protection IP40 Storage Conditions Dry Temp 10 50 C 14 122 F 30 80 rh Compliance CE EN 50270 EN 6...

Page 12: ...or any errors or omissions in this document or their consequences CGS would greatly appreciate being informed of any errors or omissions that may be found in the content of this document For informati...

Reviews: