Installation, Operation & Maintenance                                                                                   Merlin CO2 TFT

 

 

 

Rev 1   05-21 

7  

 
MIN 0-10 OUT 1  
Analogue output minimum voltage.  
Select: 

0, 1, 2, 3, 4, 5 

volt/s 

 
MIN 0-10 OUT 2  
Analogue output minimum voltage.  
Select: 

0, 1, 2, 3, 4, 5 

volt/s 

 
0-10V OUT 1  
0-10V analogue output energised by.  
Select: 

CO2 / TEMPERATURE / DUAL 

 

 
0-10V OUT 2  
0-10V analogue output energised by.  
Select: 

CO2 / TEMPERATURE / DUAL

 

 
BUZZER 
Kitchen Vent Type Mode  
CO

>2800ppm

 

Only. Select: 

ON

 

– 3 beeps every 15 seconds  

10MINS

 – 3 beeps every 10 minutes 

OFF 
 

TEMP. UNITS 
Temperature measurement 
Select: 

°C 

Celsius / 

°F 

Fahrenheit  

 

 
BOOST (MIN.) 
Analogue outputs at optimum voltage  
(10V) for number of minutes. Boost can be activated only if analogue 
outputs are set to either CO2 or DUAL mode only. 
Select: 

1, 2, 3, 4, 5, 6, 7, 8, 9, 10 

minute/s 

 
FAN ENABLE 
Fan switch is energised by.  

CO2

 (ON >600ppm   OFF <550ppm) 

TEMPERATURE

 

(ON >23°C  OFF <22°C) 

DUAL

 (Whichever is greatest) 

 
BRIGHTNESS  
Brightness of the screen display. Select: 

LOW / MEDIUM / HIGH 

 
SCREEN SAVER 

ON

 – screen will switch off until temperature or CO

2

 levels reach pre 

alarm/ alarm status.  

OFF 

 screen constantly on. 

 
TEMP. ADJUSTMENT 
Adjust the temperature display by up to ± 5°C or 9°F in increments of 

0.1°

 

 

FACTORY RESET 
Return to default condition.  

YES / NO 

    

   Factory Set Condition 

 

VENT. TYPE 

KITCH.  

BUZZER 

ON 

SCREEN SAVER 

OFF 

MIN 0-10 OUT 1 

1  

TEMP. UNITS 

°C  

TEMP. ADJUSTMENT 

0.0°C/F  

MIN 0-10 OUT 2 

1  

BOOST (MIN.) 

1  

 

 

0-10V OUT 1 

TEMP 

FAN ENABLE 

CO2  

 

 

0-10V OUT 2 

CO2 

BRIGHTNESS 

MED 

FACTORY RESET 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for Merlin CO2 TFT

Page 1: ...omatically switch between ventilation programs when gas is used Boost Mute and Wake Up feature Installation Operation Maintenance Please read this manual carefully and retain for future use The Merlin...

Page 2: ...unting 4 Board Overview 4 Wiring your CO2 TFT 5 Configuration Settings 6 Configuration 6 Factory Set Condition 7 Operation 8 Initial Power Up Indicators 8 Traffic Light Indicator 9 Alarms Configuratio...

Page 3: ...ed to replacement of the product with repaired product at the discretion of the manufacturer This warranty is void if the product has been damaged by accident unreasonable use neglect tampering or oth...

Page 4: ...here possible monitors must be fixed in such a position as to allow natural air circulation These recommended heights may vary based on airflow and temperature conditions in addition to the proposed a...

Page 5: ...n mode until the gas supply is turned off see Settings for configuration Recommended for teaching areas with gas appliances such as laboratories and food technology rooms CO2 ALARM Not a mains output...

Page 6: ...hts setting red Press to save desired setting Configuration NAT Natural Ventilation Mode Recommended for buildings without mechanical ventilation Pre Alarm 1300ppm 23 C 73 4 F Alarm 1500ppm 25 C 77 0...

Page 7: ...minutes Boost can be activated only if analogue outputs are set to either CO2 or DUAL mode only Select 1 2 3 4 5 6 7 8 9 10 minute s FAN ENABLE Fan switch is energised by CO2 ON 600ppm OFF 550ppm TEM...

Page 8: ...ears when the touch button f is pressed The audible alarm buzzer must be set to on or every 10 minutes and can only occur when gas is in use or KITCH Ventilation mode is selected and when CO2 levels r...

Page 9: ...Default Green 1500ppm 23 C 73 4 F Yellow 1500ppm 23 C 73 4 F Red 2800ppm 25 C 77 0 F CO2 Pre alarm relay switch 2800ppm CO2 Alarm relay switch 4500ppm 0 10V Analogue Output Progression Min output 1 5...

Page 10: ...e device High concentrations of alcohol found in many products may damage deteriorate or affect the gas sensing elements such as wine deodorants stain removers thinners etc Auto Calibration Our CO2 se...

Page 11: ...30mm 5 51 x 3 74 x 1 18 Unit Weight Approx 0 08kg Housing Material Polylac PA765 Environmental Ingress Protection IP40 Storage Conditions Dry Temp 10 50 C 14 122 F 30 80 rh Compliance CE EN 50270 EN 6...

Page 12: ...or any errors or omissions in this document or their consequences CGS would greatly appreciate being informed of any errors or omissions that may be found in the content of this document For informati...