background image

Installation, Operation & Maintenance                                                                                   Merlin CO2 TFT

 

 

 

Rev 1   05-21 

5  

   Wiring your CO2-TFT 

 

MAINS POWER/LINE IN  
(110-120vac option) 
Single-phase mains power is supplied to the [POWER/LINE IN] connector. 
LINE & NEUTRAL ONLY. 

 

 

 

 

GAS VALVE INPUT 
It is possible for your CO2 TFT to receive a signal from a gas solenoid valve via Live & Neutral terminals on our merlin 
panels when wired parallel. To receive a signal you must ensure that you configure the CO2 TFT to Natural or 
Mechanical ventilation mode – see settings 
for ventilation types.
  
 
 
When gas is supplied/in use – the CO2 TFT 
will receive a signal from the gas valve and 
display the [GAS IN USE] message. The CO2 
TFT will configure itself automatically to 
operate in ‘Kitchen’ mode until the gas supply 
is turned off – see ‘Settings’ for configuration. 
 
 

 

 

Recommended for teaching areas with gas appliances such as laboratories and food technology rooms. 

 

 

CO2 ALARM (Not a mains output)

 

This terminal can also connect to a building management system (BMS) or to a 
Merlin panel to send an alarm signal upon alarm levels of CO

2

. This terminal can 

also switch the Live (energise/ de-energise) a gas valve upon alarm levels of carbon 
dioxide. 

 

 

 
 
CO2 PRE-ALARM 
This relay can send a signal to a Building Management System (BMS) or Merlin 
panel when CO2 reaches pre-alarm level. 

 

 
 

FAN ENABLE  
This relay output can be connected to a fan switch which can energise fans via a 
signal. This relay will switch on a fan from the current CO

level only, by current 

temperature only or by the status of both (whichever is greatest) as follows: 

N/C: 

>600ppm / >23°C (73.4°F)  N/O: <550ppm / <22°C (71.6°F)

 

These levels cannot be altered. 

 

 

 

Summary of Contents for Merlin CO2 TFT

Page 1: ...omatically switch between ventilation programs when gas is used Boost Mute and Wake Up feature Installation Operation Maintenance Please read this manual carefully and retain for future use The Merlin...

Page 2: ...unting 4 Board Overview 4 Wiring your CO2 TFT 5 Configuration Settings 6 Configuration 6 Factory Set Condition 7 Operation 8 Initial Power Up Indicators 8 Traffic Light Indicator 9 Alarms Configuratio...

Page 3: ...ed to replacement of the product with repaired product at the discretion of the manufacturer This warranty is void if the product has been damaged by accident unreasonable use neglect tampering or oth...

Page 4: ...here possible monitors must be fixed in such a position as to allow natural air circulation These recommended heights may vary based on airflow and temperature conditions in addition to the proposed a...

Page 5: ...n mode until the gas supply is turned off see Settings for configuration Recommended for teaching areas with gas appliances such as laboratories and food technology rooms CO2 ALARM Not a mains output...

Page 6: ...hts setting red Press to save desired setting Configuration NAT Natural Ventilation Mode Recommended for buildings without mechanical ventilation Pre Alarm 1300ppm 23 C 73 4 F Alarm 1500ppm 25 C 77 0...

Page 7: ...minutes Boost can be activated only if analogue outputs are set to either CO2 or DUAL mode only Select 1 2 3 4 5 6 7 8 9 10 minute s FAN ENABLE Fan switch is energised by CO2 ON 600ppm OFF 550ppm TEM...

Page 8: ...ears when the touch button f is pressed The audible alarm buzzer must be set to on or every 10 minutes and can only occur when gas is in use or KITCH Ventilation mode is selected and when CO2 levels r...

Page 9: ...Default Green 1500ppm 23 C 73 4 F Yellow 1500ppm 23 C 73 4 F Red 2800ppm 25 C 77 0 F CO2 Pre alarm relay switch 2800ppm CO2 Alarm relay switch 4500ppm 0 10V Analogue Output Progression Min output 1 5...

Page 10: ...e device High concentrations of alcohol found in many products may damage deteriorate or affect the gas sensing elements such as wine deodorants stain removers thinners etc Auto Calibration Our CO2 se...

Page 11: ...30mm 5 51 x 3 74 x 1 18 Unit Weight Approx 0 08kg Housing Material Polylac PA765 Environmental Ingress Protection IP40 Storage Conditions Dry Temp 10 50 C 14 122 F 30 80 rh Compliance CE EN 50270 EN 6...

Page 12: ...or any errors or omissions in this document or their consequences CGS would greatly appreciate being informed of any errors or omissions that may be found in the content of this document For informati...

Reviews: