CET Electric Technology
87
Appendix C BACNet MSTP Implementation
1)
Basic Information
The PMC-53A-E supports the BACnet MS/TP protocol and can easily be connected to a BACnet
MS/TP network using an off-the shelf BACnet router. The PMC-53A-E provides four types of BACnet
objects. Standard Protocol Implementation Conformance Statement (PICS) as illustrated in table
below describes the required characteristics of the BACnet implementation.
Item
Description
Date
March 20, 2017
Vendor Name
CET
Model Name
PMC-53A-E
Applications Software Version
1.00.00
Firmware Revision
1.0
Protocol Version
1
Protocol Revision
7
Description
Intelligent Multifunction Meter
Standardized Device
BACnet Smart Actuator (B-SA)
Interoperability Building
Blocks supported
DS-RP-B, DS-RPM-B, DS-WP-B, DM-DOB-B, DM-TS-B, DM-DDB-B
Segmentation Capability
Not Supported
Data Link Layer Options
MS/TP Master, Baud rate(s): 1200, 2400, 4800, 9600, 19200,
38400
Device Address Binding
None
Networking Options
None
Character Sets Support
ANSI X3.4
2)
Device Objects
Optional Properties Supported: Description, Local_Time, Local_Date, Location
Writable
Properties:
Object_Identifier,
Number_Of_APDU_Reries,
APDU_Timeout,
System_Status, Object_Name, Location, Description, Max_Master, Max_Info_Frame,
Local_Time, Local_Date
Property Range Restrictions: Object_Identifier - valid range is between 0 and 4194302;
Object_Name - limited to 32 characters; Location - limited to 64 characters; Description -
limited to 64 characters; Max_Master – valid range is between 1 and 127.
The following table illustrates the Device Objects on the PMC-53A-E:
Property*
Description
Range/Values
Default
R/W
Object_Identifier
0 to 4194302
26001
R/W
Object_Name
Up to 32 characters
Simple Server
R/W
System_Status
Operational (0)
R
Object_Type
Device (8)
R
Vendor_Name
CET
R/W
Vendor_Identifier
593
R
Model_Name
PMC-53A-E
R
Firmware_Revision
1
R
Application_Software_Version
1.00.00
R/W
Location
Up to 64 characters
LOCAL
R/W
Description
Up to 64 characters
Intelligent
Multifunction Meter
R
Protocol_Version
1
R
Protocol_Revision
7
R
Protocol_Service_Supported
1
Please see notes below
R
Protocol_Object_Types_Supported
2
Please see notes below
R
Object_List
Please refer to sections
3) to 6)
R
Max_APDU_Length_Accepted
480
R
Segmentation
NO_SEGMENTATION
(3)
R/W
APDU_Timeout
0~65535
3000
R/W
Number_Of_APDU_Retries
0~255
3
R/W
Max_Master
1 to 127
127
R/W
Max_Info_Frame
1
R
Device_Address_Binding
{}